YASKAWA Varispeed G7 Series Instruction Manual page 165

General purpose inverter (advanced vector control)
Hide thumbs Also See for Varispeed G7 Series:
Table of Contents

Advertisement

Name
Con-
Description
stant
Display
Number
Field forcing
function
Set the field forcing function.
selection
d6-03
0: Disabled
1: Enabled
Field Force
Sel
AφR time
Set the factor to multiple
constant
times the secondary circuit
time constant of the motor to
achieve the AφR time
constant.
AφR time constant =
d6-05
Secondary circuit time
A PHI R
constant x d6-05
Filter
AφR will not function when
d6-05 is 0. If d6-05 is not 0,
the lower limit of the value
will be internally adjusted to
200 ms in the Inverter.
Field forcing
Set the excitation current ref-
limit
erence's upper limit for field
forcing. Set the limit as a per-
centage, taking the motor's
d6-06
no-load current as 100%.
FieldForce
Enabled for operation other
Limit
than DC excitation.
Usually, there is no need to
change this setting.
Control Methods
Change
Setting
Factory
during
Range
Setting
Opera-
V/f
tion
0 or 1
0
No
No
0.00 to
1.00
No
No
10.00
100 to
400%
No
No
400
User Constant Tables
MEMO-
Open
Open
BUS
V/f
Loop
Flux
Loop
Regis-
with
Vec-
Vec-
Vec-
ter
PG
tor
tor
tor
1
2
No
No
A
A
2A2H
A
No
No
No
A
2A4H
No
A
A
A
2A5H
Page
33
5-

Hide quick links: