●System command (index 2)
In the ISDU index 0x002 SystemCommand (system command), the command shown in the table below
will be issued.
The button of each system command is displayed on the IO-Link setting tool (excluding
"ParamDownloadStore").
Click the button to send the system command to the product.
Writable commands are shown below.
Data type: 8 bit UInteger
Value
Command name
(dec)
0x80
Device Reset
(128)
0x81
Application Reset
(129)
0x82
Restore Factory Settings
(130)
0xA0
All Zero Clear
(160)
0xF4
(244)
0xF5
Calibration Clear
(245)
0xF6
Calibration With +0.1%
(246)
0xF7
Calibration With -0.1%
(247)
Restarts the device
Clear the peak/bottom value of the SUP port pressure
Initialize the set value to the default value
Conduct a zero-clear of the pressure value
Calibration
Conduct calibration
Initialize the calibration status
Increase the fine adjustment rate by 0.1%
Decrease the fine adjustment rate by 0.1%