Overview - Valor LX2 CORNER Installation Manual

Direct vent zero clearance gas fireplace, natural/propane gas
Table of Contents

Advertisement

Planning
 WARNING
Ensure weight of wall above is
NOT carried by the appliance.
HeatShift front outlet
Framing—See Framing
Considerations
HeatShift ducts (4)
1/2" thick non-combustible
cement board required above
and on both sides of fi replace
opening–NOT supplied
Wall Finish
above
openin n
Combustible wall fi nish up t t o
3/4" thick allowed above openin n g
overtop of 1/2" cement board d .
Combustible projections mus s t
otherwise conform to allowable
mantel projection n s
—see p
p
p
p
age
g
g
g
Wall fi nish below opening
Combustible material up to
1-1/4" thick allowed below
opening. Combustible
projections must otherwise be
kept min. 4" below opening.
Combustible Material Allowed Beneath Fireplace.
When the appliance is installed directly on carpeting,
tile or other combustible material other than wood
fl ooring, the appliance shall be installed on a metal
or wood panel extending the full width and recessed
depth of the appliance.
 WARNING
Some materials or items, although safe,
may discolor, shrink, warp, crack, peel
and so on because of the heat produced
by the fireplace. Avoid placing candles,
paintings, photos, and other items
sensitive to heat around the fireplace.
10
g
11.
Vent collar supplied as 5 x 8" outlet, fi eld convertible to 4 x 6-5/8"
outlet (adapter supplied). Note - Vertical rise required in vent system
when adapting to 4 x 6-5/8" venting
HeatShift Plenum (front or sides) or Duct
Termination Plates (top) mandatory! HeatShift
system supplied separately—see"Appendix D -
HeatShift System" on page 72
 WARNING
HOT WALL SURFACES! The walls directly
above the fireplace are constructed of non-
combustible materials and, although safe, it
may reach temperatures in excess of
175°F depending on choice of materials. Do
not touch! Finish the walls using materials
suitable for these temperatures.

Overview

HeatShift sides outlet
Remote Battery
and Wall Switch Kit
(required) (35-foot wire
length) (supplied)
Remote
Control
Handset
Wall Holder
1/2" thick non-combustible
cement board required above
and on both sides of fi replace
opening–NOT supplied
2200K heater

Advertisement

Table of Contents
loading

This manual is also suitable for:

2200lkn2200rkn2200lkp2200rkp

Table of Contents