Ascii To Hex: Hex(117) - Omron SYSMAC CVM1 Series Operation Manual

Duplex system
Hide thumbs Also See for SYSMAC CVM1 Series:
Table of Contents

Advertisement

Conversion Instructions
Example
0000
00

5-17-15 ASCII TO HEX: HEX(117)

Ladder Symbol
(117)
HEX S Di D
Variations
↑HEX(117)
Description
Digit Designator
When CIO 000000 is ON in the following example, the status of bits 00 to 15 in
D00005 are copied consecutively to bits number 08 of D00010 through D00025,
with the status of bit 00 being transferred to bit 08 of D00010.
(116)
COLM D00005
D00010
#0008
Operand Data Areas
S: First source word
Di: Digit designator
D: Destination word
When the execution condition is OFF, HEX(117) is not executed. When the
execution condition is ON, HEX(117) converts the data in specified source
words from ASCII to hexadecimal data, and outputs the results to a specified
destination word.
The ASCII range that can be converted is the numerals 0 through 9 ($30 through
$39) and the capital letters A through F ($41 through $46).
If an attempt is made to convert other data, the Error Flag will turn ON and the
instruction will not be executed.
The digit designator, Di, specifies the first digit to receive the converted data, the
number of digits to be converted, the first ASCII data to be converted, and the
parity (see below).
Digit number: 3 2 1 0
Data in the destination word (D) will not be changed except for the digits that are
converted to hexadecimal.
Address Instruction
00000
00001
CIO, G, A, T, C, DM
CIO, G, A, T, C, #, DM, DR, IR
CIO, G, A, DM
Specifies the first digit to receive converted data (0 to 3)
Number of digits to be converted (0 to 3)
0: 1 digit
1: 2 digits
2: 3 digits
3: 4 digits
First ASCII data to be converted.
0: Rightmost 8 bits
1: Leftmost 8 bits
Parity
0: None
1: Even
2: Odd
Section 5-17
Operands
LD
000000
COLM(116)
D00005
D00010
#0008
227