Programming Devices; Compatible Programming Devices - Omron SYSMAC CVM1 Series Operation Manual

Duplex system
Hide thumbs Also See for SYSMAC CVM1 Series:
Table of Contents

Advertisement

Programming Devices

1-7

Programming Devices

1-7-1 Compatible Programming Devices

Connecting Cables
Allowed Number of
Programming Devices
There are three Programming Devices that can be used with CVM1D PCs: The
SYSMAC Support Software (SSS), the Programming Console and the Data Ac-
cess Console.
Name
SYSMAC Support Software
(C500-ZL3AT1-E)
Programming Console
(CVM1-PRS21-EV1)
Data Access Console
(CV500-DAC11)
Note
1. If the SYSMAC-CPT Support Software is used, AR Area words unique to the
CVM1D PCs cannot be programmed. Furthermore, programs containing
these AR Area words cannot be transferred.
2. Errors that have been added to the CVM1D (the duplex bus error, duplex
verification error, and duplex power supply error) will not be displayed on
Programming Consoles other than the CVM1-PRS21-EV1 version 2.0.
These errors will not be displayed in the error history, either.
The following table shows which cables can be used when connecting a host
computer or Programming Console to the Duplex Unit's peripheral connector.
Make the required connecting cable when connecting to the host link connector.
Programming Device
Personal Computer (SSS)
Programming Console
g
g
A total of four Programming Consoles can be connected to a CVM1D PC, as
shown in the following table. Only one Programming Console can be connected
to the CPU Unit or an I/O Interface Unit.
If a Programming Console is connected to the CPU or an I/O Interface Unit, 3
more Programming Devices can be connected to SYSMAC BUS/2 Remote I/O
Slave Units. If no Programming Console is connected to the CPU Unit or I/O In-
terface Unit, 4 Programming Consoles can be connected to SYSMAC BUS/2
Remote I/O Slave Units. Up to 2 Programming Consoles can be connected to
Remote I/O Slaves under a single Remote I/O Master Unit.
Connecting Unit
CPU Unit
CV500-II201
I/O Interface Unit
SYSMAC BUS/2
Slave Unit
The SYSMAC Support Software (SSS) is the main
Programming Device used to program and monitor
CVM1D PCs. You must have the SSS to program
and operate these PCs.
The Programming Console can be used for onsite
monitoring and programming of PC, but does not
support advanced programming/debugging
operations.
Use a version 2.0 or higher Programming Console
with CVM1D PCs. Earlier versions cannot perform
online I/O Unit replacement.
The Data Access Console can be used for onsite
monitoring and and setting adjustments.
Cable model number
CV500-CIF01
CV500-CN224
CV500-CN424
CV500-CN624
Max. connection
combinations
1
0
0
The same functions are supported when
connected to either Unit.
0
1
0
3
3
4
The I/O Table Register, I/O Table
Change, and SYSMAC LINK Broadcast
Test operations are not supported.
Section 1-7
Function
Cable length
6 m
2 m
4 m
6 m
Comments
pp
d
i h
U i
7