Ladder Diagram Instructions

5-6-4 NOT: NOT(010)

Description
Precautions
Flags
Example
0000
0005
00
02
0000
12

5-6-5 AND LOAD and OR LOAD

AND LOAD: AND LD
Ladder Symbol
000000
000002
000001
000003
Description
Flags
Ladder Symbol
(010)
NOT
NOT(010) reverses the execution condition.
NOT(010) is an intermediate instruction that inverts the execution condition that
precedes it. As an intermediate instruction, it cannot be placed at the end of an
instruction line, only between conditions or between a condition and a right-hand
instruction.
NOT(010) cannot be used as right-hand instructions, i.e., another instruction
must appear between them and the right bus bar.
There are no flags affected by NOT(010).
The following example and bit status table show the operation of NOT(010).
0005
(001)
NOT
(001)
END
Bit
000000
ON
OFF
000012
ON
ON
000502
ON
ON
000505
OFF
OFF
When instructions are combined into blocks that cannot be logically combined
using only OR and AND operations, AND LD and OR LD are used. Whereas
AND and OR operations logically combine a bit status and an execution condi-
tion, AND LD and OR LD logically combine two execution conditions, the current
one and the last unused one.
AND LD and OR LD are not necessary when drawing ladder diagrams or when
inputting ladder diagrams using ladder diagram programming. They are re-
quired, however, to convert the program to and input it in mnemonic form.
In order to reduce the number of programming instructions required, a basic un-
derstanding of logic block instructions is required. For an introduction to logic
blocks, refer to 4-4-1 Logic Block Instructions.
There are no flags affected by these instructions.
Address Instruction Operands
05
Bit status
ON
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
ON
OR LOAD: OR LD
Ladder Symbol
000000
000001
000002
000003
Section 5-6
00000
LD
000000
00001
OR
000012
00002
AND
000502
00003
NOT(010)
---
00004
OUT
000505
00005
END(001)
---
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
111