Comparison Instructions
0000
00
(029)
CMPL
0010
A50005
(GR)
A50006
(EQ)
A50007
(LE)
206
• If the content of CIO 0011 and CIO 0010 is equal to that of CIO 0009 and
CIO 0008, then output CIO 002001 will turn ON.
• If the content of CIO 0011 and CIO 0010 is less than that of CIO 0009 and
CIO 0008, then output CIO 002002 will turn ON.
0008
0020
00
0020
01
0020
02
S
+ 1 = 0011
1
1234
Comparison Results
A50005 (GR)
A50006 (EQ)
A50007 (LE)
S
+ 1 = 0010
1
5678
Comparison
OFF
OFF
ON
Section 5-16
Address Instruction
Operands
00000
LD
00001
CMPL(029)
00002
AND
00003
OUT
00004
AND
00005
OUT
00006
AND
00007
OUT
S
+ 1 = 0009
S
+ 1 = 0008
2
2
ABCD
EF12
000000
0010
0008
A50005
002000
A50006
00201
A50007
002002

Advertisement