Eaton 91PS UPS 8-40 kW User And Installation Manual page 79

Table of Contents

Advertisement

Eaton 91PS/93PS UPS 8–40 kW
Figure 34. Options for relay outputs configuration
7.
Enter the code(s) of the function(s) that you want to trigger the relay when
they become active.
8.
Press OK and Save to save the changes.
Figure 35. Entering the codes of the functions that will trigger the relay
9.
If you selected one of the MiniSlots, the following default values are
available:
Alternatively, you can configure the relays with any event you want.
©
Eaton Corporation plc 2018. All rights reserved.
Relay 1: #262 On Line (LED is lit)
Relay 2: #260 On Battery (LED is lit)
Relay 3: #416 Alarm (LED is lit)
Relay 4: #261 On Bypass (LED is lit)
Relay 5: #15 Low Battery warning
Revision: 005
Document ID: P-164000493
User's and installation guide
79 (117)

Advertisement

Table of Contents
loading

This manual is also suitable for:

93ps ups 8-40 kw

Table of Contents