Eaton 91PS/93PS UPS 8–40 kW
3.3.3
The Power Conditioner mode is characterized by the UPS running in the double
conversion mode without batteries connected. In the Power Conditioner mode,
the UPS provides conditioned output voltage and frequency. The UPS can also
support high nonlinear loads without ITHD on the input. The UPS meets the
qualifications outlined in this product specification, except for the conditions
below.
When in the Power Conditioner mode, the UPS has the following functionality
and limitations:
1.
The UPS runs in the double conversion mode.
2.
Because there is no battery, loss of utility power results in the UPS losing
power and shutting down.
3.
The UPS sustains up to -50% input voltage tolerance, unless the current
limit is reached.
4.
If the rectifier is turned off, the UPS attempts a transfer to the bypass
mode.
5.
The ESS mode is not available.
3.3.4
The Frequency Converter mode is characterized by the UPS running without the
bypass mode available. The output frequency can be configured to be different
from the standard input frequency (e.g. 60 Hz output, 50 Hz input). The UPS
can also support high nonlinear loads without iTHD on the input. The UPS
meets the qualifications outlined in this product specification, except for the
conditions below.
When in the Frequency Converter mode, the UPS has the following functionality
and limitations:
1.
Operation is the same as when in the double conversion mode with no
bypass available.
2.
Bypass alarms are suppressed.
3.4
3.4.1
MiniSlot Communication Bays — there are 2 communication bays for MiniSlot
connectivity cards. MiniSlot cards are quickly installed and are hot-pluggable.
See Chapter
©
Eaton Corporation plc 2018. All rights reserved.

Power Conditioner

Frequency Converter

Software and connectivity features

User interface

6
for additional information.
Revision: 005
Document ID: P-164000493