Eaton 91PS/93PS UPS 8–40 kW
Note: Maximum number of internal batteries are included with all the models (except the
C-model, which has no internal batteries).
The UPS cabinets use forced air cooling to regulate internal component
temperature. By default, air inlets are in the front of the cabinet and outlets are
in the back. Allow clearance in front of and behind each cabinet for proper air
circulation.
The clearance required around the UPS cabinet is shown in Table
Note: This equipment is not intended for building-in, rack-mounting or for
incorporation in larger equipment.
Table 9: UPS cabinet minimum clearances
From the top of the cabinet
From the front of the cabinet
From the back of the cabinet
From the side of the cabinet
* Applies to the 20 kW C-model frame as well.
©
Eaton Corporation plc 2018. All rights reserved.
C-model 8-20 kW
frame
15/20 kW frame*
Revision: 005
User's and installation guide
15/20 kW
frame
500 mm
650 mm
150 mm
0 mm
Document ID: P-164000493
30/40 kW
frame
9
.
30/40 kW frame
500 mm
650 mm
250 mm
0 mm
36 (117)