Wire entry for the battery breaker signal wiring is located in the middle of the
UPS cabinet. Punch holes are located on the left or right side panel, back wall or
bottom plate.
See Section
5.5.3
The general alarm relay is a dry relay signal output. The relay can be used for
informing the operators about UPS alarm conditions, for example through a
building management system. By default, the relay is configured to activate
when the UPS general alarm is active, that is, any event when the
status is active. The relay can also be configured to activate by some other
event, but this needs to be done by authorized service personnel. The relay
rating is 30 V AC or DC, 5 A.
Relay signal wiring can be installed only through the signal cabling canal, from
back to front, in the top section of the UPS.
Additional relay outputs are available with mini-slot cards. Relay outputs can be
configured to be activated by various events. Configuration can be done by an
authorized Eaton Customer Service Engineer or by other qualified service
personnel authorized by Eaton.
5.5.4
Relays K1 through K5 are identical in function. Each output contact function can
be assigned by the user. The UPS information may also be configurable.
To install the INDRELAY-MS:
1.
Check that the ancillary equipment system is turned off and all the power
sources are removed. Refer to the appropriate operation manual of any
ancillary equipment for shutdown instructions.
2.
Install wiring from the IRC to the monitoring equipment using appropriate
conduits through the cable exit opening in the IRC.
3.
Connect wiring between the IRC terminal blocks and the monitoring
equipment using terminations. Connect one wire to COM (Common) and
another to either NC or NO to select the Normally Open or Normally Closed
option.
4.
Install the INDRELAY-MS into an open MiniSlot communication bay in the
UPS cabinet.
©
Eaton Corporation plc 2018. All rights reserved.
5.2.1
for installation instructions.

Relay output interface connections

Industrial Relay Card interface connections

Revision: 005
Document ID: P-164000493
User's and installation guide
ALARM
62 (117)