Eaton 91PS/93PS UPS 8–40 kW
User's and installation guide
Figure 29. PX Gateway Card
Note: PX Gateway Card is not compatible with 91PS units.
Industrial Relay Card-MS
The MiniSlot Industrial Relay Card provides a way of connecting the 91PS/
93PS to industrial and electrical monitoring systems. It also enables a wide
range of control applications by allowing up to 250 volts and 8 Amperes
through its 5 relay connections. By connecting wires to the corresponding
places in its terminal blocks, you can choose Normally Open or Normally
Closed setup for each output.
For information on how to configure Industrial Relay Card-MS, see Section
6.6
.
Figure 30. Industrial Relay Card-MS
©
Eaton Corporation plc 2018. All rights reserved.