Eaton 91PS/93PS UPS 8–40 kW
Rated
power
[kW]
15
20
30
40
Notes:
1.
Maximum rectifier current calculated at the -15% voltage tolerance and 102% con-
tinuous overload.
2.
Maximum output/bypass current calculated at continuous 125% overload and at
-15% voltage tolerance.
3.
Maximum battery current calculated at rated load and 1.67 V cell voltage for the
default 32 block string length.
Table 16: 91PS rated and maximum currents for rated power and voltage (3-phase input,
1-phase output models)
Rated pow-
er
[kW]
8
10
15
©
Eaton Corporation plc 2018. All rights reserved.
Rectifier input
Rated
Rated
Maximum
voltage
current
[V]
[A]
380
24
400
23
415
22
380
32
400
30
415
29
380
48
400
45
415
44
380
64
400
60
415
58
Rated voltage
Rated cur-
[V]
380
400
415
380
400
415
380
400
415
UPS output / bypass
Rated
Maximum
current
current
[A]
[A]
28
23
27
22
26
21
37
31
36
29
34
28
56
46
53
44
51
43
75
62
71
59
69
57
Rectifier input
Maximum cur-
rent
rent
[A]
[A]
18
18
17
18
17
18
21
22
20
22
19
22
29
29
28
29
27
29
Revision: 005
Document ID: P-164000493
User's and installation guide
Battery
Rated
Maximum
current
current
[A]
[A]
34
41
32
41
31
41
45
55
42
55
41
55
67
82
64
82
61
82
89
110
85
110
82
110
UPS out-
put / bypass
Rated cur-
Rated cur-
rent
[A]
36
35
33
45
43
42
68
65
63
current
[A]
49
49
49
66
66
66
98
98
98
131
131
131
Battery
rent
[A]
22
22
22
28
28
28
42
42
42
43 (117)