Maintenance; System Maintenance Procedures; Adding A Rectifier Or Converter Module To An Existing Module Mounting Assembly Spec. No. 588705300 - Vertiv 582127000100 User Manual

-48 vdc power system
Hide thumbs Also See for 582127000100:
Table of Contents

Advertisement

4 Maintenance

4.1 System Maintenance Procedures

It is recommended to perform the maintenance procedures listed in Table 4.1 every 6-months to ensure continual system operation.
Table 4.1 Maintenance Procedures to be Performed at 6-Month Intervals
Procedure
Check ventilation openings for obstructions
such as dust, papers, manuals, etc.
Inspect and tighten all installer's connections.
4.2 Adding a Rectifier or Converter Module to an Existing Module Mounting
Assembly Spec. No. 588705300
To increase system current capacity, a rectifier module can easily be added to an existing module mounting assembly Spec. No.
588705300 that contains an empty rectifier module mounting position. Likewise, to increase subsystem capacity a -48 VDC to
+24 VDC DC-DC converter module can be added to a module mounting assembly Spec. No. 588705300 that contains an empty
-48 VDC to +24 VDC converter module mounting position. A -48 VDC to -58 VDC DC-DC converter module can be added to a
module mounting shelf that contains an empty -48 VDC to -58 VDC converter module mounting position.
Rectifier and converter modules can be inserted or removed with power applied (hot swappable).
Rectifiers modules can be installed in any mounting position of each module mounting assembly. Converter modules can be installed
in any of the three far right mounting positions of the three lower module mounting assemblies (as viewed from the front). See
Figure 4.3. See Alerts below for restrictions.
NOTE!
Each rectifier and converter module locks into the module mounting assembly by means of a latch located on the
bottom of the module. The latch and module handle are interactive. Pushing the handle up into the module's front panel
causes the latch to extend to the locking position; pulling the handle down out from the module's front panel causes the latch
to retract. See Figure 4.3.
WARNING!
To prevent damage to the latching mechanism, ensure the handle is in the open position when installing or
removing a module. NEVER hold the handle in the closed position when installing a module into a shelf.
ALERT! The system can either have +24V DC-DC converters installed or -58V DC-DC converters installed. The system
cannot have both types of converters installed at the same time.
ALERT! The -48 VDC to +24 VDC converter modules must only be installed in a system position that accepts a +24V DC-DC
converter. Refer to labeling on the system's module mounting shelf. A sample of this labeling is provided in Figure 4.1.
Figure 4.1 Sample Module Mounting Shelf Labeling
Referenced In
--
IM582127000100,
"Making Electrical Connections" section.
Proprietary and Confidential © 2022 Vertiv Group Corp.
Vertiv™ NetSure™ 7100 Series -48 VDC Power System User Manual