P 101
Auto Acceleration/Deceleration
00
Linear acceleration/deceleration
01
Auto acceleration, linear deceleration
Settings
02
Linear acceleration, auto deceleration
03
Auto acceleration/deceleration
04
Linear Accel/Decel Stall Prevention during Deceleration
When this parameter is set to 03, the AC drive will accel/decel in the
fastest and smoothest possible way by automatically adjusting the
accel /decel time.
This parameter provides five modes to choose:
00 Linear acceleration and deceleration (operation by P10, P11, or P12,
P13 acceleration/deceleration time)
01 Automatic acceleration, linear deceleration (Operation by automatic
acceleration,P11 or P13 deceleration time).
02 Linear acceleration and automatic deceleration (Operation by automatic
deceleration time, P10 or P12 acceleration time).
03 Automatic acceleration, deceleration (Operation by AC drive auto
adjustable control)
04 If this parameter is set to 04, Accel/Decel time will be equal to or more
than parameter P10 ~P13.
This parameter should not be used when a brake unit is installed.
P 102
Auto Voltage Regulation (AVR)
00
AVR function enabled
01
AVR function disabled
Settings
02
AVR function disabled when stop
03
AVR function disabled for deceleration
Usually Motor rated voltage are AC220V/380V.50HZ/60HZ, 220V
inverter input voltag e AC180V-264V, 50HZ/60HZ.So if inverter don't
have Auto Voltage Regulation function, if inverter power is AC260V,
the voltage to motor also will be AC260V,the motor is running exceed
-106-
Chapter 6 Parameters
Factory Setting
00
Factory Setting
00
12~20%Auto Voltage Regulation% rated voltage. Motor temperature
will rise, insulating ability damage. Torque output unstable. The life-
span of the motor will accelerate shorten and cause loss.
When input voltage exceed motor's rated voltage. The inverter's AVR
function can automatic stable the input voltage. For example: V/F curve
set as AC220V/50HZ. When the input power is between AV220V-264V.
the voltages will auto stable to AC220V/50HZ then supply to motor,
When input voltage between AC180V-210V,the motor voltage will
proportional to input power
When we found motor deceleration stop, close AVR will short deceleration
time. With auto Acceleration/Deceleration function. The deceleration
of motor will be much faster
Auto Tune Motor parameters
P 103
Disable
00
Settings
Auto tune for R1
01
Auto tune for R1 + No Load testing
02
For Auto Tune, set P103 to 01 or 02 and press the RUN key. When it is
set to 02, motor should have no load.
P 104
R1 Value
Settings
00 to 65535m
As an option to Auto Tune, this parameter inputs the motor resistance.
Control mode
P 105
00
V/F Control
Settings
01
Sensor-less Vector Control
Rated Slip
P 106
Settings
0.00 to 10.00 Hz
-107-
Chapter 6 Parameters
Factory Setting
00
Factory Setting
00
Factory Setting
00
Factory Setting
3.0