Chziri ZVF200-M User Manual page 40

Vector inverter
Table of Contents

Advertisement

Sheet 6-2 Two wire command operation sheet
Two Wire operation 1
Switch status
Operation Command 1
K1
K2
OFF
OFF
RUN
ON
OFF
FWD
OFF
ON
REV
ON
ON
STOP
SWITCH ON is on . SWITCH OFF is OFF.
Fig.6-11 Two wire control 1/2
02: Three Wire control
See Pig 6-12 . X3 is three wire operation control stop terminal
K1
FWD
K2
REV
K3
STOP
When the "2" setting is selected for P38. The value is P39 will be ignored .
Multi-function Input Terminal (X3)
P 39
P 40
Multi-function Input Terminal (X4)
P 41
Multi-function Input Terminal (X5)
Multi-function Input Terminal (X6)
P 42
Settings
00 to 32
-74-
Chapter 6 Parameters
Two Wire operation 2
Operation Command 2
STOP
FWD
STOP
REV
Fig.6-12 Three wire control
Factory Setting
05
Factory Setting
06
Factory Setting
07
Factory Setting
08
Settings
Function
00
No Function
Output OFF (N.O.)
(enabled when
01
When it is set to 01 or 02, AC drive output will stop
running)
immediately. If there is start signal after stopping,
Output OFF (N.C.)
the output will start from the minimum frequency.
(enabled when
02
running)
Parameter values 3 and 4 program Multi-Function
Input Terminals: X1,X2 (P38), X3 (P39), X4
External Fault
03
(P40), X5 (P41) or X6 (P42) to be External
(N.O.)
Fault (E.F.) inputs.
Note: When an External Fault input signal is
received, the AC drive output will turn off,
drive will display "E.F." on Digital Keypad,
External Fault
and the motor will coast. Normal operation
04
(N.C.)
can resume after the External Fault is cleared
and the AC drive is reset.
When an External Fault input signal is received .
E.g. the drive will display EF ,OH , OC .OV ect .
05
External Reset
The External Reset has the same function as the
Reset key on the Digital keypad. It will reset the
drive after a fault.
These three inputs select up to seven multi-step
Multi-Step Speed
speeds defined by P17 to P23 as shown in the
06
Command 1
following diagram. It can reach to multi-step
speeds if main speed connect to jog.
P78 to P87 can also control output speed by
programming the AC drive's internal PLC function.
Multi-Step Speed
07
The terminal control for Multi-step speed . Refer
Command 2
to Sheet 6-3.
-75-
Chapter 6 Parameters
Description

Advertisement

Table of Contents
loading

Table of Contents