These functions are used to change acceleration or deceleration depending
on attained frequency and not by closing contacts on the external
terminals. The priority of this parameter is higher than the time of
Accel/Decel 1 and Accel/Decel 2.
Auto energy-saving
P 95
Disable auto energy-saving operation
01
Settings
Enable auto energy-saving operation
02
When this function is enabled, the AC drive operates at full voltage
during speed changes. At the constant speed periods, drive calculates
the optimal output voltage value for the load and may get it reduced
up to 30% below the Maximum Output Voltage.
Rated Frequency
Fig. 6-29 Energy saving run output
Count Down Completion
P 96
Settings
00 to 9999
This parameter defines the top count value for the ZVF200-M internal
counter. Please also see P45 and P46 (setting 13). Counting is in
cremented when the Multi-Function Input Terminal X1 or X2, makes
a low-to-high transition. Upon completion of the count, either Multi-
Function Output Terminal (XO1) or the Multi-Function Relay Contact
(RA, RB) will close.
-104-
Chapter 6 Parameters
Factory Setting
00
Factory Setting
00
Preset Count Down Completion
P 97
Settings
00 to 9999
When count value start at c01 and reached the parameter set. The selected
multi function output terminal will close.Reliminary count could be
used to initiate an external event before the terminal count is reached.
Before stop can choose this as output signal let the inverter low move
till stop.See Fig.6-30.
Display
value
Counter
trigger signal
Preset count down
completion output
Count down
output
Fig. 6-30 Count Down Completion
Total Time Count from Power On (Days)
P 98
Settings
00 to 65535 days
Total Time Count from Power On (Minutes)
P 99
Settings
00 to 1440 minutes
This parameter shows the inverter Cumulative time. It will not return
to zero while Restore production value.
P 100
Software Version
This parameter shows the software version for the AC motor drive.
-105-
Chapter 6 Parameters
Factory Setting
00
the width of counter trigger
Signal is lower than 2ms
( 250Hz)
Factory Setting
Factory Setting
Factory Setting