Explanation
Settings
Parameter
PLC FWD/REV
P79
00 to 127
Motion
P80
Reserved
Time Duration of
P81
00 to 9999 sec
1st Step Speed
Time Duration of
P82
00 to 9999 sec
2nd Step Speed
Time Duration of
P83
00 to 9999 sec
3rd Step Speed
Time Duration of
P84
00 to 9999 sec
4th Step Speed
Time Duration of
P85
00 to 9999 sec
5th Step Speed
Time Duration of
P86
00 to 9999 sec
6th Step Speed
Time Duration of
P87
00 to 9999 sec
7th Step Speed
Communication
P88
01 to 254
Address
00: 4800 bps
01: 9600 bps
Transmission
P89
Speed
02: 19200 bps
03: 38400 bps
-52-
Chapter 6 Parameters
Factory
Default
Min.
Unit
Setting
Unit
Setting
1
00
s
1
00s
s
1
00s
s
1
00s
s
1
00s
s
1
00s
s
1
00s
s
1
00s
1
01
1
01
Explanation
Settings
Parameter
00: Warn and Continue Operating
Transmission
01: Warn and RAMP to Stop
Fault
02: Warn and COAST to Stop
P90
Treatment /Stop
03: Keep Operation without
mode selection
Warning
Time Out
0.0: Disable
P91
Detection
0.1 to 120.0 sec
00: MODBUS ASCII mode,
<7,N,2>
01: MODBUS ASCII mode,
<7,E,1>
02: MODBUS ASCII mode,
Communication
<7,O,1>
P92
data format
03: MODBUS RTU mode,
selection
<8,N,2>
04: MODBUS RTU mode,
<8,E,1>
05: MODBUS RTU mode,
<8,O,1>
Accel 1 to Accel 2
0.01 to 400.0Hz
P93
Frequency
0.00: Disable
Transition
Decel 1 to Decel 2
0.01 to 400.0Hz
P94
Frequency
0.00: Disable
Transition
Auto Energy
00: Disable auto energy saving
P95
Saving
01: Enable auto energy saving
Counter Countdown
P96
00 to 9999
Complete
Preset counter
P97
00 to 9999
countdown
-53-
Chapter 6 Parameters
Factory
Default
Min.
Unit
Setting
Unit
Setting
1
03
s
0.1
0.0s
1
00
Hz
0.1 0.00Hz
Hz
0.1 0.00Hz
1
00
1
00
1
00