Chziri ZVF200-M User Manual page 31

Vector inverter
Table of Contents

Advertisement

Explanation
Settings
Parameter
00: Input positive PID feedback,
PV from A VI (0 to 10V)
01: Input negative PID feedback,
PID Feedback
PV from A VI (0 to 10V)
P116
Terminal
02: Input positive PID feedback,
Selection
PV from ACI (4 to 20mA)
03: Input negative PID feedback,
PV from ACI (4 to 20mA)
Proportional
P117
0.0 to 10.0
Gain (P)
P118 Integral Time (I) 0.01 to 100.0 sec
Differential
P119
0.00 to 1.00 sec
Time (D)
Integration's Upper
P120
00 to 100 %
Bound Frequency
PID One-Time
P121
0.0 to 2.5 sec
Delay
PID Frequency
P122
Output
00 to 110 %
Command Limit
Feedback Signal
0.0: Disable
P123
Detection Time
0.1 to 3600 sec
00: Warning and RAMP to stop
Feedback Signal
P124
01: Warning and keep operating
Fault Treatment
Source of PID
P125
0.00 to 400.0Hz
Set Point
P126
PID Offset Level
1.0 to 50.0 %
-56-
Chapter 6 Parameters
Factory
Default
Min.
Unit
Setting
Unit
Setting
1
00
0.1
1.0
s
0.01
1.00s
s
0.01
0.00s
%
1
100%
s
0.1
0.0s
%
1
100%
s
0.1
60.0s
1
00
Hz
0.1 0.00Hz
%
0.1
10.0%
Explanation
Settings
Parameter
Detection Time
P127
0.1 to 300.0 sec
of PID Offset
Minimum
P128
0.0 to 10.0 V
Reference Value
Maximum
P129
0.0 to 10.0 V
Reference Value
Invert Reference
00: Not inverted
Signal AVI
P130
01: Inverted
(0-10V)
Minimum
Reference
P131
0.0 to 20.0mA
Value (4-20mA)
Maximum
Reference
P132
0.0 to 20.0mA
Value (4-20mA)
Invert Reference
00: Not inverted
P133
Signal (4-20mA)
01: Inverted
Analog Input
P134
Delay Filter for
00 to 9999
Set Point
Analog Input
Delay Filter for
P135
00 to 9999
Feedback Signal
Sleep Period
P136
0.0 to 6550.0 sec
Sleep Frequency
P137
0.00 to 400.0 Hz
Wake Up
P138
0.00 to 400.0 Hz
Frequency
-57-
Chapter 6 Parameters
Factory
Default
Min.
Unit
Setting
Unit
Setting
s
0.1
5.0s
V
0.1
0.0V
V
0.1
10.0V
1
00
mA
0.1
4.0mA
mA
0.1 20.0mA
1
00
1
50
1
5
s
0.1
0.0s
Hz
0.1 0.00Hz
Hz
0.1 0.00Hz

Advertisement

Table of Contents
loading

Table of Contents