Over-Torque Detection Mode
P 60
00
Over-Torque detection disabled.
Enabled during constant speed operation until the allowable
01
time for detection (P62) elapses.
Settings
Enabled during constant speed operation and halted after detection.
02
Enabled during acceleration until the allowable time for
03
detection (P62)elapses.
Enabled during acceleration and halted after detection.
04
P 61
Over-Torque Detection Level
Settings
30 to 200%
A setting of 100% is proportional to the Rated Output Current of the
drive.This parameter sets the Over-Torque Detection level in 1%
increments. (The AC drive rated current is equal to 100%.)
Over-Torque Detection Time
P 62
Settings
0.0 to 10.0sec
This is the duration for over-torque detection. When the output current
is larger than the overtorque detection level (P61), an over-torque
condition exists and the detection time (P62) is timed-out. Any of the
multi-function output terminals set to indicate over-torque, will then
close. (Please refer to P45 and P46)
P 63
Loss of ACI (4-20mA)
Decelerate to 0 Hz
00
Settings
Stop immediately and display "EF"
01
Continue operation by last frequency command
02
-92-
Chapter 6 Parameters
Factory Setting
00
Factory Setting 150%
Factory Setting 0.1sec
Factory Setting
00
User Defined Function for Display
P 64
Displays AC drive output frequency (Hz)
00
Display User-defined output Frequency (H*P65)
01
Output Voltage (E)
02
DC Bus Voltage (u)
03
PV (i)
04
Settings
Displays the value of the internal counter (c)
05
Displays the setting Frequency (F)
06
Displays the parameter setting (P)
07
Reserved
08
Output Current (A)
09
Display program operation (0. xxx), Fwd, or Rev
10
The parameter can be set to display the user-defined value. (where v
= H x P65 )
P 65
Coefficient K
Settings
0.01 to 160.0
The coefficient K determines the multiplying factor for the user-defin ed
unit.
The display value is calculated as follows:
Display value = output frequency
The display window is only capable of showing four digits, yet you
could use P65 to create larger numbers. The display windows uses
decimal points to signify numbers up to three digits as illustrated in
next page:
If it display "9999". the actual value is 9999.If it display "9999.". the
actual value is the display value
actual value is the display value
Communication Frequency
P 66
Settings
0.00 to 400.0 Hz
This parameter defines the Master Frequency when the AC drive is
controlled by the communication interface.
-93-
Chapter 6 Parameters
Factory Setting
00
Factory Setting
1.00
K
10=99990.If it display "999.9". the
100=999900.
Factory Setting
0.00