Explanation
Settings
Parameter
DC Braking
P28
00 to 100 %
Current Level
DC Braking
P29
0.0 to 5.0 sec
during Start-up
DC Braking
P30
0.0 to 25.0 sec
during Stopping
Start-point for
P31
0.00 to 60.00 Hz
DC Braking
00: Stop operation after
momentary power loss
01: Continues after momentary
Momentary
power loss, speed search
Power Loss
starts with Master Frequency
P32
Operation
02: Continues after momentary
Selection
power loss, speed search
starts with Minimum output
Frequency
Maximum
P33
Allowable
0.3 to 5.0 sec
Power Loss Time
Base-Block Time
P34
0.3 to 5.0 sec
for Speed Search
Maximum Current
P35
Level for Speed
30 to 200%
Search
Upper Bound of
P36
0.10 Hz to 400.0Hz
Output Frequency
-44-
Chapter 6 Parameters
Factory
Default
Min.
Unit
Setting
Unit
Setting
%
1
00%
s
0.1
0.0s
s
0.1
0.0s
Hz
0.1 0.00Hz
1
00
s
0.1
2.0s
s
0.1
0.5s
%
1
150%
Hz
0.1 400.0Hz
Explanation
Settings
Parameter
Lower Bound of
P37
0.00 Hz to 400.0Hz
Output Frequency
00: X1: FWD/STOP,
Multi-function
X2: REV/STOP
Input
01: X1: RUN/STOP,
P38
Terminal
X2: REV/FWD
(X1,X2)
02: X1, X2, X3: 3-wire
operation control mode
00: No Function
01: Output OFF (NC) (enabled
when running)
Multi-function
02: Output OFF (NO) (enabled
when running)
Input
P39
03: External Fault (normally
Terminal (X3)
open) (NO)
04: External Fault (normally
close) (NC)
05: RESET
06: Multi-Step Speed
Command 1
07: Multi-Step Speed
Multi-function
Command 2
Input
P40
08: Multi-Step Speed
Terminal (X4)
Command 3
09: Jog Operation
10: Accel/Decel Speed Inhibit
11: First or Second Accel/Decel
Time
12: Base-block (B.B.) (NO)
13: Base-block (B.B.) (NC)
14: Increase Master Frequency
Multi-function
15: Decrease Master Frequency
Input
P41
16: Run PLC Program
Terminal (X5)
17: Pause PLC
18: Counter Trigger Signal
19: Counter Reset
20: No function
-45-
Chapter 6 Parameters
Factory
Default
Min.
Unit
Setting
Unit
Setting
Hz
0.1 0.00Hz
1
00
1
05
1
06
1
07