Explanation
Settings
Parameter
Motor Rated
30.0%
120.0% rated output
P52
Current
current
Motor No-Load
P53
00%FLA to 99%FLA
Current
Torque
P54
00 to 10
Compensation
Slip
P55
0.00 to 10.00
Compensation
P56
Reserved
AC Drive Rated
Current Display
P57
(unit: 0.1A)
00: Standard Motor (self cool
Electronic
motor)
Thermal
P58
01: Inverter Motor (auxiliary
Overload Relay
cool fan on motor)
02: Inactive
Electronic Thermal
P59
30 to 300 sec
Motor Overload
00: Over-Torque Detection
Disable
01: Enabled during constant
speed operation until the
Over-Torque
P60
allowable time for detection
Detection Mode
elapses.
02: Enabled during constant
speed operation and halted
after detection.
-48-
Chapter 6 Parameters
Factory
Default
Min.
Unit
Setting
Unit
Setting
According
A
0.1
to request
A
0.1
0.4*P52
1
00
0.01
0.00
1
02
s
1
60s
1
00
Explanation
Settings
Parameter
03: Enabled during acceleration
until the allowable time for
Over-Torque
P60
detection elapses.
Detection Mode
04: Enabled during acceleration
and halted after detection.
Over-Torque
P61
30 to 200%
Detection Level
Over-Torque
P62
0.0 to 10.0 seconds
Detection Time
00: Decelerate to 0 Hz
01: Stop immediately and
display "EF"
P63
Loss of ACI
02: Continue operation by last
frequency command
00: Display AC drive output
Frequency (Hz)
01: Display User-defined output
Frequency (H*P65)
02: Output Voltage (E)
03: DC Bus V oltage (u)
04: PV (i)
User Defined
05: Display the value of internal
Function
counter (c)
P64
06: Display the setting frequency
for Display
(F )
07: Display the parameter setting
(P)
08: Reserved
09: Output Current (A)
10: Display program operation
(0.xxx), Fwd, or Rev
P65
Coefficient K
0.01 to 160.0
-49-
Chapter 6 Parameters
Factory
Default
Min.
Unit
Setting
Unit
Setting
1
00
%
150%
1
s
1
0.1s
1
00
1
06
0.01
1.00