Chziri ZVF200-M User Manual page 54

Vector inverter
Table of Contents

Advertisement

P 80
Reserve
Settings
none
P 81
Time Duration of 1st Step Speed
P 82
Time Duration of 2nd Step Speed
P 83
Time Duration of 3rd Step Speed
P 84
Time Duration of 4th Step Speed
P 85
Time Duration of 5th Step Speed
Time Duration of 6th Step Speed
P 86
P 87
Time Duration of 7th Step Speed
Settings
00 to 9999 second
P81 to P87 input the duration of each Multi-step speed operation defined
by P17 to P23.
when the parameter set to 00 (0 sec), the corresponding step
operation will be skipped. Although supply 7 duration .User
can reduce duration to 5 or 3 when necessary, Just set the no
TIP
need duration parameter to 00(0 sec).
P 88
Communication Address
Settings
01 to 254
This parameter sets the AC drive address identification when using the
RS-485 serial port for communication.
P 89
Transmission Speed (Baud rate)
00
4800 bps
01
9600 bps
Settings
02
19200 bps
03
38400 bps
Set and amend the inverter inside parameter and control inverter running,
detect inverter status.This parameter sets the transmission speed of
computer and inverter.
-102-
Chapter 6 Parameters
Factory Setting
Factory Setting
00
Factory Setting
00
Factory Setting
00
Factory Setting
00
Factory Setting
00
Factory Setting
00
Factory Setting
00
Factory Setting
01
Factory Setting
01
This parameter sets the transmission speed for communication on the
RS485 serial port.
P 90
Transmission Fault Treatment/Stop mode selection
00
Warn and Continue Operating
01
Warn and RAMP to Stop
Settings
02
Warn and COAST to Stop
Keep Operation without Warning
03
P 91
Time Out Detection
0.1 to 120.0 sec
Settings
0.0 disable
Start timing when received the first valid data. If overtime still hasn't
received the second data .it will show "CE10" .can 'RESET' or External
terminals reset.
P 92
Communication Protocol
00
Modbus ASCII mode, <7,N,2>
01
Modbus ASCII mode, <7,E,1>
02
Modbus ASCII mode, <7,O,1>
Settings
03
Modbus RTU mode, <8,N,2>
04
Modbus RTU mode, <8,E,1>
05
Modbus RTU mode, <8,O,1>
Each AC drive has a pre-assigned communication address specified
by P88. The master controller communicates with each AC drive
according to its particular address. Detail way please see appendix.
Accel 1 to Accel 2 Frequency Transition
P 93
P 94
Decel 1 to Decel 2 Frequency Transition
0.0: disable
Settings
0.1 to 400.0 Hz
-103-
Chapter 6 Parameters
Factory Setting
03
Factory Setting
0.0
Factory Setting
00
Factory Setting
0.00
Factory Setting
0.00