Jog Accel / Decel Time
P 15
Settings
0.01 to 600.0 sec
This parameter sets the acceleration or deceleration time for Jog operation.
Jog Frequency
P 16
Settings
0.00 to 400.0 Hz
When the JOG function is activated, the AC drive will accelerate from
Minimum Output Frequency (P08) to Jog Frequency (P16). Drive must
be in "stop" status for the operator to activate the JOG function. Likewise,
during Jog operation, other commands cannot be accepted through the
keypad but FORWARD, REVERSE and STOP. The JOG function can
be remotely activated when the Jog terminal is closed , and if the Jog
terminal opens, the AC drive will decelerate from Jog Frequency to
zero. The accel / decel time is entered as Jog Accel / Decel Time (P15).
Multi-function Input terminals (X1-X5) can also be used to initiate
the JOG operation if so programmed.
Fig.6-6 Jog Operation and Acceleration/Deceleration Time
-66-
Chapter 6 Parameters
Factory Setting 1.0 sec
Factory Setting 6.00Hz
1st step speed output frequency
P 17
2nd step speed output frequency
P 18
P 19
3rd step speed output frequency
4th step speed output frequency
P 20
5th step speed output frequency
P 21
6th step speed output frequency
P 22
7th step speed output frequency
P 23
Settings
0.00 to 400.0Hz
Multi-Function Input Terminals (refer to P39 to P42) are used to select
Multi-Step speeds. The desired speed frequencies are entered in P17
to P23. When the associated multifunction input terminal is closed,
drive will run at one of these specific frequencies.
Multi-step speeds (P17 to P23), P78, P79, and P81 to P87; are used
for multi-step motion cont rol, which is executed in an orderly manner,
similar to a PLC program.
P 24
Reverse Operation Inhibition
00 Enable REV operation
Settings
01 Disable REV operation
This parameter is used to disable motor rotation in reverse.
P 25
Over-Voltage Stall Prevention
00
Disable
Settings 220V series
330-450Vdc
380V series
660-900Vdc
During deceleration, the DC bus voltage may exceed its maximum
allowable value due to motor regeneration. When this function is
enabled, the AC drive will stop decelerating, and maintain a constant
output frequency to prevent from over-voltage tripping. Drive will
resume deceleration when the voltage drops below the setting for P25.
-67-
Chapter 6 Parameters
Factory Setting
0.00Hz
Factory Setting
0.00Hz
Factory Setting
0.00Hz
Factory Setting
0.00Hz
Factory Setting
0.00Hz
Factory Setting
0.00Hz
Factory Setting
0.00Hz
Factory Setting
00
Factory Setting 390/780