Beckhoff EL9 Series Documentation page 53

Ethercat system terminals
Table of Contents

Advertisement

Technical data
Technical data
Nominal voltage
Power contact current load
Electrical isolation
Integrated fine-wire fuse
Current consumption from E-Bus
Bit width in the process image
Configuration
Power LED
Diagnosis (fuse)
Electrical connection to mounting rail
PE contact
Renewed infeed
Connection facility to additional power con-
tact
Side by side mounting on Bus Terminals with
power contact
Side by side mounting on Bus Terminals
without power contact
Weight
Permissible ambient temperature range (dur-
ing operation)
Permissible ambient temperature range (dur-
ing storage)
Permissible relative humidity
Dimensions (W x H x D)
Mounting [} 73]
Vibration/shock resistance
EMC resistance burst/ESD
Protect. class
Installation pos.
Approval
Connection EL9250, EL9260
Hazard to individuals and devices!
When designing a Bus Terminal block with different potentials on the power contacts (e.g. 230 V AC and 24
V DC), please note that it is mandatory to use potential separation terminals (EL9080)!
Bring the bus system into a safe, powered down state before starting installation, disassembly or wiring of
the Bus Terminals!
Terminal point
Indication
No.
230 V AC
1
N
2
PE
3
230 V AC
4
N
5
PE
6
EL9xxx
EL9250
230 V AC
max. 10 A
500 V (E-bus/field potential)
yes; 6.3 A
-
-
no address or configuration settings
yes
yes, Error LED
no
yes
yes
1
yes
yes
approx. 55 g
0°C ... +55°C
-25°C ... +85°C
95%, no condensation
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conforms to EN 60715
conforms to EN 60068-2-6/EN 60068-2-27
conforms to EN 61000-6-2/EN 61000-6-4
IP 20
variable, see chapter "Mounting of Passive
Terminals [} 83]"
CE
CAUTION
Description
Supply input 230 V AC;
connected internally with terminal 4 and 230 V AC power contact)
N for supply input;
connected internally with terminal 5 and neutral power contact)
PE;
connected internally with terminal 6 and PE power contact)
Supply input 230 V AC;
connected internally with terminal 1 and 230 V AC power contact)
N for supply input;
connected internally with terminal 2 and neutral power contact)
PE;
connected internally with terminal 3 and PE power contact)
Version: 3.9
Product overview
EL9260
typ. 90 mA
2 bit (diagnosis)
yes, in process image and Error LED
variable
53