Beckhoff EL9 Series Documentation page 18

Ethercat system terminals
Table of Contents

Advertisement

Product overview
The EL9080 separation terminal interrupts the power contacts within a bus terminal block. The terminal
enables operation with different voltages on the separated sides of the power contacts. But the K-Bus is
looped through. The discontinuance of the Power Contacts is especially displayed by the orange front plate
of the EL9080. The EL9080 separation terminal does not have any other function or connection facility.
Technical Data
Electrical isolation
Bit width in the process image
Configuration
Diagnosis
PE contact
Renewed infeed
Connection facility to additional
power contact
Side by side mounting on Bus
Terminals with power contact
Side by side mounting on Bus
Terminals without power contact
Electrical connection to mounting
rail
Weight
Permissible ambient temperature
Permissible ambient temperature
range (during storage)
Permissible relative humidity
Dimensions (W x H x D)
Mounting [} 73]
Vibration/shock resistance
EMC resistance burst/ESD
Protect. class
Installation pos.
Approval
18
EL9011
-
0
no address or configuration settings
-
no
-
-
yes
yes
no
approx. 8 g
-25°C ... +60°C (extended temperature range)
-40°C ... +85°C
95%, no condensation
approx. 8 mm x 100
mm x 34 mm
(width aligned: 5 mm)
aligned to the last terminal in the terminal block on 35 mm mounting rail
conforms to EN 60068-2-6/EN 60068-2-27
conforms to EN 61000-6-2/EN 61000-6-4
IP 20
variable
CE
ATEX [} 85]
cULus [} 86]
Version: 3.9
EL9012
approx. 10 g
approx. 8 mm x 100
mm x 55 mm (width
aligned: 5 mm)
EL9080
500 V (E-bus/field
potential)
approx. 40 g
approx.15 mm x 100
mm x 70 mm
(width aligned: 12 mm)
conforms to EN 60715
EL9xxx