Beckhoff EL9 Series Documentation page 36

Ethercat system terminals
Table of Contents

Advertisement

Product overview
Technical data
Technical Data
Nominal voltage
Current load
Diagnosis
Message to E-Bus
PE contact
Shield connection
Current consumption from E-Bus
Bit width in the process image
Electrical connection to mounting
rail
Electrical isolation
Renewed infeed
Side by side mounting on EtherCAT
Terminals with power contact
Side by side mounting on EtherCAT
Terminals without power contact
Connection facility to additional
power contact
Configuration
Weight
Permissible ambient temperature
range (during operation)
Permissible ambient temperature
range (during storage)
Permissible relative humidity
Dimensions (W x H x D)
Mounting [} 73]
Vibration/shock resistance
EMC resistance burst/ESD
Protect. class
Installation pos.
Approval
Connection EL9185
Terminal point
Indication
Output 1, 2 ,5, 6
Output 3, 4, 7, 8
36
EL9185
arbitrary up to 230 V AC/DC
≤ 10 A
-
-
no
-
-
0
-
500 V (E-bus/field potential)
-
only 2 power contacts, no PE
-
4
no address or configuration settings
approx. 65 g
-25°C ... +60°C (extended temperature range)
-40°C ... +85°C
95%, no condensation
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conforms to EN 60715
conforms to EN 60068-2-6/EN 60068-2-27, see Installation
instructions [} 76] for enhanced mechanical load capacity
conforms to EN 61000-6-2/EN 61000-6-4
IP 20
variable, see chapter "Mounting of Passive Terminals [} 83]"
CE
ATEX [} 85]
cULus [} 86]
Description
No.
1, 2 ,5, 6
Output 1, 2 ,5, 6
(internally connected with positive power contact)
3, 4, 7, 8
Output 3, 4, 7, 8
(internally connected with negative power contact)
Version: 3.9