Beckhoff EL9 Series Documentation page 46

Ethercat system terminals
Table of Contents

Advertisement

Product overview
Technical data
Technical data
Technology
Power contact current load
Power LED
Defect LED
Current consumption from E-Bus
Nominal voltage
Integrated fine-wire fuse
Electrical isolation
Diagnosis
Reported to E-bus
Power contact
PE contact
Renewed infeed
Connection facility to additional power con-
tact
Side by side mounting on Bus Terminals with
power contact
Side by side mounting on Bus Terminals
without power contact
Shield connection
Electrical connection to mounting rail
Bit width in the process image
Configuration
Weight
Permissible ambient temperature range (dur-
ing operation)
Permissible ambient temperature range (dur-
ing storage)
Permissible relative humidity
Dimensions (W x H x D)
Mounting [} 73]
Vibration/shock resistance
EMC resistance burst/ESD
Protect. class
Installation pos.
Approval
Connection EL9195
Hazard to individuals and devices!
When designing a Bus Terminal block with different potentials on the power contacts (e.g. 230 V AC and 24
V DC), please note that it is mandatory to use potential separation terminals (EL9080)!
Bring the bus system into a safe, powered down state before starting installation, disassembly or wiring of
the Bus Terminals!
46
EL9195
shield terminal, for dissipation of EMC interference
max. 10 A
-
-
-
arbitrary up to 230 V AC/DC
-
500 V (E-bus/field potential)
-
-
2 x power contact
-
-
2
only 2 power contacts
-
2 x
yes
-
no address or configuration settings
approx. 50 g
0°C ... +55°C
-25°C ... +85°C
95%, no condensation
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conform to EN 60715
conforms to EN 60068-2-6/EN 60068-2-27
conforms to EN 61000-6-2/EN 61000-6-4
IP 20
variable, see chapter "Mounting of Passive Terminals [} 83]"
CE
ATEX [} 84]
cULus [} 86]
CAUTION
Version: 3.9
EL9xxx