3 DirectPWM Interface Connection Procedure
3
Click the Open Loop Step Test button.
The motor is performing reciprocating
operation and the test result on the
right is displayed.
If the motor does not rotate, change
the Test Amplitude parameter to a
large value.
The test result is when the Test
Amplitude parameter is set to 8.0%.
3-6-2

Current Loop Gain Setting

Follow the procedure below to perform current loop gain settings and adjust them to achieve desired
response characteristics.
1
In the Tune screen, select Current
Loop Tuning ‒ Interactive Tune.
2
Set the following parameters.
IliGain: 0.0099999998 (Default)
IpfGain: 0
IpbGain: 0
Magnitude: 3000 bits
Dwell Time: 50 ms
3-20
CK3M/CK5M Series Startup Guide DirectPWM Interface (O047)