Terminator Resistor Settings

2.4
According to the ISO 11898 specifications, the CAN Bus network
must be terminated by two terminal resistors (120
following figure.
Therefore, the I-7530A-MR module supplies a jumper for activating
the terminal resistor. If users want to use this terminal resistor, please
open the I-7530A-MR cover and use the JP3 to activate the 120
resistor built in the module, as the Figure 2-9. Note that the default setting
is active.
I-7530A-MR Modbus RTU to CAN Converter User's Manual (Version 1.08, 07/2019) ------------- 14
Figure 2-8: Terminal Resistor
Figure 2-9: Terminal Resistor Jumper
Ω
). They are shown as
Ω
terminal