Applications; Functional Description; Interfaces - Bender COMTRAXX CP9 Series Manual

Remote alarm indicator and operator panel for medical locations and other areas
Hide thumbs Also See for COMTRAXX CP9 Series:
Table of Contents

Advertisement

3.7

Applications

• Optimal visualisation on the display tailored to the user
• Integration of all compatible Bender products (ISOMETER®, ATICS®, RCMS, EDS, Linetraxx® and MEDICS®
systems, universal measuring devices and energy meters)
• Individual instructions in case of alarms
• Selective noti cation to various users in case of alarms
• Control and regulation of systems such as air conditioning or blinds control.
3.8

Functional description

3.8.1

Interfaces

CP9xx communicate with the devices and systems assigned via various interfaces:
• Internal BMS bus (RS-485) for Bender systems such as EDS46.../49..., RCMS46.../49... and MEDICS®. CP9xx
can be operated as a master or as a slave. When operated as a master, requests are answered more quickly.
The devices can only be operated on the internal BMS bus.
• BCOM (Ethernet) for new and future Bender systems, such as ISOMETER® iso685-D.
• Modbus RTU (RS-485) CP9xx when operated as a master for Bender devices PEM... with restricted
functionality (full functionality of PEM...5 only via Modbus TCP).
• Modbus RTU (RS-485)
COM465...P when operated as a master for Bender devices PEM... with restricted functionality (full
functionality of PEM...5 only via Modbus TCP).
• Modbus TCP (Ethernet) for Bender devices PEM...5
COMTRAXX® CP9xx – Control Panel