GENERAL DESCRIPTION

The Fire Suppression system is specifically
designed for controlling wet chemical fires
in the fryer.
The system consists of a cylinder assembly
(with pressure switch and gauge), actuating
lever, (2) fusible link assemblies, manual pull
station and two nozzles.

AUTOMATIC OPERATION

Upon the detection of a fire, the system will
automatically operate. The fusible link in the
cooking area separates at a temperature of
280° F, which allows the spring to pull down
on the actuating lever. The valve stem is
pushed down releasing pressure and wet
chemical to the nozzles. If the heat contin-
ues to rise the fusible link in the fan com-
partment separates and allows the fire
damper to drop to prevent any flames, if
present, from exiting the cabinet.

MANUAL OPERATION

When the manual pull handle on the front
panel is pulled, the system operates simi-
larly by disconnecting the fusible link cable
from the actuating lever. The spring pulls
down on the lever releasing pressure and
wet chemical to the nozzles.

3 -FIRE SUPPRESSION SYSTEM

IMPORTANT:
The manual
pull handle is to
be pulled ONLY
IN CASE OF
FIRE in the
fryer (use when
the automatic
system has
failed).
broaster.com Manual #16501 8/06 Rev 01-22
psi, the pressure switch opens, deacti-
vating the power relay cutting all power
to the fryer.
INSPECTION & MAINTENANCE
dures are detailed in Section 3, Fire
Suppression Maintenance and Replace-
ment of the VF-2/VF-3i Service & Parts
Manual.
The Fire Suppression system must be ser-
viced on a regular basis. Three types of ser-
vicing are required: Monthly, Semi-Annually,
and 12 Year. Prior to any inspection, the Fire
Suppression system needs to be exposed.

Gaining Access

To gain access to the Fire Suppression sys-
tem remove Electrical Control Access
Panel.
1. Disconnect main power.
2. Remove retaining screw.
3. Slide the panel up to clear retaining
tabs.
4. Pull the bottom toward the outside of
the unit.
3-1
If the pressure in the cyl-
inder drops below 195
Selected fire suppres-
sion maintenance proce-