Integration into BACnet Systems

6.3. Integration into BACnet Systems
NOTICE
You can see the Protocol Implementation Conformance Statement (PICS) document in
https://www.intesis.com/docs/bacnet-client-pic-statement-776

6.3.1. BACnet Objects

NOTICE
This part is common for BACnet MS/TP and BACnet/IP.
Input object types:
• Binary input.
Output object types:
• Binary output.
• Multistate output.
• Analog output.
The following tables list all available BACnet objects for this gateway.
Table 7. Global signals
Object instance
Type
15000 + 0
3-Binary Input
15000 + 0
4-Binary Output
15000 + 0
14-Multistate Output
15000 + 0
1-Analog Output
15000 + 1
14-Multistate Output
15000 + 1
4-Binary Output
Table 8. Outdoor units
Object instance
(OU[1 .. 12]*20) + 10000 + 0
0-Analog Input
(OU[1 .. 12]*20) + 10000 + 1
0-Analog Input
(OU[1 .. 12]*20) + 10000 + 2
0-Analog Input
(OU[1 .. 12]*20) + 10000 + 3
0-Analog Input
(OU[1 .. 12]*20) + 10000 + 4
0-Analog Input
(OU[1 .. 12]*20) + 10000 + 5
0-Analog Input
(OU[1 .. 12]*20) + 10000 + 6
0-Analog Input
(OU[1 .. 12]*20) + 10000 + 7
0-Analog Input
(OU[1 .. 12]*20) + 10000 + 8
0-Analog Input
(OU[1 .. 12]*20) + 10000 + 9
0-Analog Input
(OU[1 .. 12]*20) + 10000 + 10
0-Analog Input
(OU[1 .. 12]*20) + 10000 + 11
0-Analog Input
(OU[1 .. 12]*20) + 10000 + 12
0-Analog Input
(OU[1 .. 12]*20) + 10000 + 13
0-Analog Input
(OU[1 .. 12]*20) + 10000 + 14
0-Analog Input
(OU[1 .. 12]*20) + 10000 + 15
0-Analog Input
(OU[1 .. 12]*20) + 10000 + 16
0-Analog Input
USER MANUAL Version 1.2
Possible values
0-No error, 1-Error
0-Off, 1-On
1-Heat, 2-Cool, 3-Fan, 4-Dry, 5-Auto
ºC / ºF
1-Low, 2-Medium, 3-High, 4-Powerful
0-Unlock, 1-Lock
Type
Possible values
Hz
OUXX_Compressor 1 Frequency
Hz
OUXX_Compressor 2 Frequency
ºC / ºF
OUXX_Heat Exchange low 1 temperature
ºC / ºF
OUXX_Heat Exchange low 2 temperature
ºC / ºF
OUXX_Heat Exchange low 3 temperature
ºC / ºF
OUXX_Heat Exchange low 4 temperature
ºC / ºF
OUXX_Heat exchange high 1 temperature
ºC / ºF
OUXX_Heat exchange high 2 temperature
ºC / ºF
OUXX_Heat exchange high 3 temperature
ºC / ºF
OUXX_Heat exchange high 4 temperature
ºC / ºF
OUXX_Unit temperature
ºC / ºF
OUXX_Discharge pipe 1 temperature
ºC / ºF
OUXX_Discharge pipe 2 temperature
ºC / ºF
OUXX_Crankcase temperature 1
ºC / ºF
OUXX_Crankcase temperature 2
Amperes
OUXX_Compressor current 1
Amperes
OUXX_Compressor current 2
Mitsubishi Heavy Industries VRF with KNX, Serial and IP support
Object name
Gateway Communication Status
On/Off (all units)
Mode (all units)
Setpoint
FanSpeed (all units)
Remote Lock
Object name
Unit 1 .. Unit 12
Unit 1 .. Unit 12
Unit 1 .. Unit 12
Unit 1 .. Unit 12
Unit 1 .. Unit 12
Unit 1 .. Unit 12
Unit 1 .. Unit 12
Unit 1 .. Unit 12
Unit 1 .. Unit 12
Unit 1 .. Unit 12
Unit 1 .. Unit 12
Unit 1 .. Unit 12
Unit 1 .. Unit 12
Unit 1 .. Unit 12
Unit 1 .. Unit 12
Unit 1 .. Unit 12
Unit 1 .. Unit 12
Unit ID
OU
1 .. 12
1 .. 12
1 .. 12
1 .. 12
1 .. 12
1 .. 12
1 .. 12
1 .. 12
1 .. 12
1 .. 12
1 .. 12
1 .. 12
1 .. 12
1 .. 12
1 .. 12
1 .. 12
1 .. 12