Samsung NASA with KNX, Serial and IP support

6.3. Integration into BACnet Systems

NOTICE
You can see the Protocol Implementation Conformance Statement (PICS) document on
www.intesis.com/docs/bacnet-client-pic-statement-770

6.3.1. BACnet Objects

NOTICE
This part is common for BACnet MS/TP and BACnet/IP.
Input object types:
• Binary input
Output object types:
• Binary output
• Multistate output
• Analog output
The following tables list all available BACnet objects for this gateway.
Table 8. Error signals
Object name
OUXX_Communication Error OU
OU Addressing Error
Table 9. Global signals
Object name
On/Off (all units)
Mode (all units)
FanSpeed (all units)
Vane position swing (all units)
Temperature Setpoint (all units)
Vent. On/Off (all units)
Page 34 of 44
Possible values
0: No error
1: Error
0: OU Addressing OK
1: Manual Addr in OU required
Possible values
0: Off
1: On
1: Heat
2: Cool
3: Fan
4: Dry
5: Auto
6: Cool Storage
7: Heat Storage
1: Low
2: Mid
3: High
4: Auto
0: Swing Off
1: Swing On
Cool: 18 .. 30°C / 64 .. 86°F
Heat: 16 .. 30°C / 61 .. 86°F
0: Off
1: On
Integration into BACnet Systems
Object type
Object instance
3-Binary Input
OU[0..15]+1
3-Binary Input
0+16
Object type
Object instance
4-Binary Output
0+0
14-Multistate Output
0+0
14-Multistate Output
0+1
4-Binary Output
0+1
1-Analog Output
0+0
4-Binary Output
0+2
USER MANUAL Version 1.0.6