Connection Procedure For Home Automation - HMS Networks Intesis IN776MHI00XO000 User Manual

Mitsubishi heavy industries vrf with knx, serial and ip support
Table of Contents

Advertisement

Mitsubishi Heavy Industries VRF with KNX, Serial and IP support

5.2.6. Connection Procedure for Home Automation

NOTE
Remember to check the
1. Connect the Home Automation Ethernet cable to the gateway's Ethernet Port.
IMPORTANT
Use a straight Ethernet UTP/FTP CAT5 or higher cable.
IMPORTANT
If communicating through the LAN of the building, contact the network administrator and make
sure traffic on the used port is allowed through all LAN paths.
NOTE
When commissioning the gateway for the first time, DHCP will be enabled for 30 seconds. After
that time, the default IP 192.168.100.246 will be set.
2. Use the supplied USB Mini-B type to A type cable to connect the gateway, through its USB port, to a PC to
configure it with Intesis MAPS.
NOTICE
Find all you need to know about the gateway configuration and Intesis MAPS in the
IN776MHI00xO000 Gateway Configuration Guide.
NOTICE
See the wiring diagram in the Figure:
Page 18 of 36
Common Connections (page
General view of all gateway connectors (page 10)
12).
Connection
USER MANUAL Version 1.2