Mitsubishi Heavy Industries VRF with KNX, Serial and IP support
6.3. Integration into BACnet Systems
NOTICE
You can see the Protocol Implementation Conformance Statement (PICS) document on
www.intesis.com/docs/bacnet-client-pic-statement-776
6.3.1. BACnet Objects
NOTICE
This part is common for BACnet MS/TP and BACnet/IP.
Input object types:
• Binary input
Output object types:
• Binary output
• Multistate output
• Analog output
The following tables list all available BACnet objects for this gateway.
Table 8. Global signals
Object name
Gateway Communication Status
On/Off (all units)
Mode (all units)
Setpoint
FanSpeed (all units)
Remote Lock
Table 9. Outdoor units
Object name
OUXX_Compressor 1 Frequency
OUXX_Compressor 2 Frequency
OUXX_Heat Exchange low 1 temperature
OUXX_Heat Exchange low 2 temperature
OUXX_Heat Exchange low 3 temperature
OUXX_Heat Exchange low 4 temperature
OUXX_Heat exchange high 1 temperature
Page 30 of 36
Possible values
Type
0: No error
3-Binary Input
1: Error
0: Off
4-Binary Output
1: On
1: Heat
14-Multistate Output
2: Cool
3: Fan
4: Dry
5: Auto
°C / °F
1-Analog Output
1: Low
14-Multistate Output
2: Medium
3: High
4: Powerful
0: Unlock
4-Binary Output
1: Lock
Possible values
Hz
Hz
°C / °F
°C / °F
°C / °F
°C / °F
°C / °F
Integration into BACnet Systems
Object instance
15000 + 0
15000 + 0
15000 + 0
15000 + 0
15000 + 1
15000 + 1
Type
Object instance
0-Analog Input
(OU[1 .. 12]×20) + 10000 + 0
0-Analog Input
(OU[1 .. 12]×20) + 10000 + 1
0-Analog Input
(OU[1 .. 12]×20) + 10000 + 2
0-Analog Input
(OU[1 .. 12]×20) + 10000 + 3
0-Analog Input
(OU[1 .. 12]×20) + 10000 + 4
0-Analog Input
(OU[1 .. 12]×20) + 10000 + 5
0-Analog Input
(OU[1 .. 12]×20) + 10000 + 6
https://
USER MANUAL Version 1.2.7