Integration Into Home Automation Systems; Home Automation Signals - HMS Networks Intesis IN776MHI00XO000 User Manual

Mitsubishi heavy industries vrf with knx, serial and ip support
Table of Contents

Advertisement

Integration into Home Automation Systems

6.4. Integration into Home Automation Systems

6.4.1. Home Automation Signals

The following tables list all available Home Automation signals for this gateway.
NOTE
SET: Command used to control the indoor unit. It is sent by the client.
CHN: Command used to get notifications of changes in the status of a specific function of the
gateway. It is sent spontaneously by the gateway itself.
GET: Command used to get the status of a specific function. It is sent by the client.
To know more about the Home Automation protocol, see the
Table 10. Indoor units
Description
On/Off
Operation Mode
Fan Speed
Vane Position
Temperature Setpoint
(x10) (16 .. 30ºC)
AC Ambient Temperature
(x10) (0 .. 30ºC)
Unit Error code (0-No Error, X-
Error)
Error IU
USER MANUAL Version 1.2
acNum
Function
Values
1
ONOFF
ON/OFF
HEAT/COOL/FAN/DRY/
1
MODE
AUTO
LOW/MED/HIGH/
1
FANSP
POWERFUL
1
VANEUD
1/2/3/4/SWING
1
SETPTEMP
(ºC)
1
AMBTMP
(ºC)
1
ERRCODE
0/X
1
ERRSTATUS
OK/ERR
Mitsubishi Heavy Industries VRF with KNX, Serial and IP support
Protocol specifications
Commands
Unit ID
(See Note)
SET/CHN/GET
Unit 1 .. Unit 128
SET/CHN/GET
Unit 1 .. Unit 128
SET/CHN/GET
Unit 1 .. Unit 128
SET/CHN/GET
Unit 1 .. Unit 128
SET/CHN/GET
Unit 1 .. Unit 128
CHN/GET
Unit 1 .. Unit 128
CHN/GET
Unit 1 .. Unit 128
CHN/GET
Unit 1 .. Unit 128
manual.
IU
OU
1 .. 128
1 .. 12
1 .. 128
1 .. 12
1 .. 128
1 .. 12
1 .. 128
1 .. 12
1 .. 128
1 .. 12
1 .. 128
1 .. 12
1 .. 128
1 .. 12
1 .. 128
1 .. 12