Mitsubishi Heavy Industries VRF with KNX, Serial and IP support
Status_OU Unit temperature
Status_OU Discharge pipe temperature 1
Status_OU Discharge pipe temperature 2
Status_OU Crankcase temperature 1
Status_OU Crankcase temperature 2
Status_OU Compressor current 1
Status_OU Compressor current 2
Status_OU High pressure
Status_OU Low pressure
Table 6. Indoor units
Description
Status_CommError
0-No error, 1-Error
Control_On/Off
0-Off, 1-On
Status_On/Off
0-Off, 1-On
0-Auto, 1-Heat, 3-Cool, 9-Fan, 14-
Control_Operation mode
Dry
0-Auto, 1-Heat, 3-Cool, 9-Fan, 14-
Status_Operation mode
Dry
Control_Operation mode
0-Auto, 1-Heat, 2-Dry, 3-Fan, 4-Cool
Status_Operation mode
0-Auto, 1-Heat, 2-Dry, 3-Fan, 4-Cool
Control_Operation mode
0-Cool, 1-Heat, 2-Fan, 3-Dry, 4-Auto
Status_Operation mode
0-Cool, 1-Heat, 2-Fan, 3-Dry, 4-Auto
Control_Mode Cool/Heat
0-Cool, 1-Heat
Status_Mode Cool/Heat
0-Cool, 1-Heat
Control_Auto mode
1-Set auto mode
1-Auto mode active, 0-Auto mode
Status_Auto mode
not active
Control_Heat mode
1-Set heat mode
1-Heat mode active, 0-Heat mode
Status_Heat mode
not active
Control_Cool mode
1-Set cool mode
1-Cool mode active, 0-Cool mode
Status_Cool mode
not active
Control_Fan mode
1-Set fan mode
1-Fan mode active, 0-Fan mode not
Status_Fan mode
active
Control_Dry mode
1-Set dry mode
1-Dry mode active, 0-Dry mode not
Status_Dry mode
active
Control_Temperature
16..30ºC / 60..86ºF
setpoint
Status_Temperature
16..30ºC / 60..86ºF
setpoint
Page 28 of 36
ºC / ºF
9.001/9.027-DPT_Value_Temp (2byte)
ºC / ºF
9.001/9.027-DPT_Value_Temp (2byte)
ºC / ºF
9.001/9.027-DPT_Value_Temp (2byte)
ºC / ºF
9.001/9.027-DPT_Value_Temp (2byte)
ºC / ºF
9.001/9.027-DPT_Value_Temp (2byte)
Amperes
14.019-DPT_Value_Electric_Current (4byte)
Amperes
14.019-DPT_Value_Electric_Current (4byte)
MPa
14.058-DPT_Value_Pressure (4byte)
MPa
14.058-DPT_Value_Pressure (4byte)
Function
1.005-DPT_Alarm (1bit)
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
20.105-DPT_HVACContrMode
(1byte)
20.105-DPT_HVACContrMode
(1byte)
5.x (1byte)
5.x (1byte)
5.x (1byte)
5.x (1byte)
1.100-DPT_Heat/Cool (1bit)
1.100-DPT_Heat/Cool (1bit)
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
9.001/9.027-DPT_Value_Temp
(2byte)
9.001/9.027-DPT_Value_Temp
(2byte)
Integration into KNX Systems
R, T
Unit 1 .. Unit 12
R, T
Unit 1 .. Unit 12
R, T
Unit 1 .. Unit 12
R, T
Unit 1 .. Unit 12
R, T
Unit 1 .. Unit 12
R, T
Unit 1 .. Unit 12
R, T
Unit 1 .. Unit 12
R, T
Unit 1 .. Unit 12
R, T
Unit 1 .. Unit 12
DPT
Flags
R, T
Unit 1 .. Unit 128
Ri, W, U
Unit 1 .. Unit 128
R, T
Unit 1 .. Unit 128
Ri, W, U
Unit 1 .. Unit 128
R, T
Unit 1 .. Unit 128
Ri, W, U
Unit 1 .. Unit 128
R, T
Unit 1 .. Unit 128
Ri, W, U
Unit 1 .. Unit 128
R, T
Unit 1 .. Unit 128
Ri, W, U
Unit 1 .. Unit 128
R, T
Unit 1 .. Unit 128
Ri, W, U
Unit 1 .. Unit 128
R, T
Unit 1 .. Unit 128
Ri, W, U
Unit 1 .. Unit 128
R, T
Unit 1 .. Unit 128
Ri, W, U
Unit 1 .. Unit 128
R, T
Unit 1 .. Unit 128
Ri, W, U
Unit 1 .. Unit 128
R, T
Unit 1 .. Unit 128
Ri, W, U
Unit 1 .. Unit 128
R, T
Unit 1 .. Unit 128
Ri, W, U
Unit 1 .. Unit 128
R, T
Unit 1 .. Unit 128
USER MANUAL Version 1.2
1 .. 12
1 .. 12
1 .. 12
1 .. 12
1 .. 12
1 .. 12
1 .. 12
1 .. 12
1 .. 12
Unit ID
IU
1 .. 128
1 .. 128
1 .. 128
1 .. 128
1 .. 128
1 .. 128
1 .. 128
1 .. 128
1 .. 128
1 .. 128
1 .. 128
1 .. 128
1 .. 128
1 .. 128
1 .. 128
1 .. 128
1 .. 128
1 .. 128
1 .. 128
1 .. 128
1 .. 128
1 .. 128
1 .. 128