HMS Networks Intesis IN776MHI00XO000 User Manual page 28

Mitsubishi heavy industries vrf with knx, serial and ip support
Table of Contents

Advertisement

Integration into Modbus Systems
Table 2. Outdoor unit registers
Modbus address
R/W
(OU[1..12]*20)+4000+1
R
(OU[1..12]*20)+4000+2
R
(OU[1..12]*20)+4000+3
R
(OU[1..12]*20)+4000+4
R
(OU[1..12]*20)+4000+5
R
(OU[1..12]*20)+4000+6
R
(OU[1..12]*20)+4000+7
R
(OU[1..12]*20)+4000+8
R
(OU[1..12]*20)+4000+9
R
(OU[1..12]*20)+4000+10
R
(OU[1..12]*20)+4000+11
R
(OU[1..12]*20)+4000+12
R
(OU[1..12]*20)+4000+13
R
(OU[1..12]*20)+4000+14
R
(OU[1..12]*20)+4000+15
R
(OU[1..12]*20)+4000+16
R
(OU[1..12]*20)+4000+17
R
(OU[1..12]*20)+4000+18
R
(OU[1..12]*20)+4000+19
R
Table 3. Indoor unit registers
Modbus address
R/W
(U[0..127]*20)+1
R
Communication Status
(U[0..127]*20)+2
RW
On/Off
(U[0..127]*20)+3
RW
Operation Mode
(U[0..127]*20)+4
RW
Temperature Setpoint (x10)
(U[0..127]*20)+5
RW
Fan Speed
(U[0..127]*20)+6
RW
Remote Lock
(U[0..127]*20)+7
RW
Louver / Vane Position
(U[0..127]*20)+8
R
Room Temperature (x10)
(U[0..127]*20)+9
R
Filter Sign Status
(U[0..127]*20)+10
R
Unit Error code
(U[0..127]*20)+11
R
Compressor Status
(U[0..127]*20)+12
W(T)
Filter Sign Reset
(U[0..127]*20)+13
W(T)
RC Error Reset
USER MANUAL Version 1.2
Register Name
OU Compressor 1 Frequency
OU Compressor 2 Frequency
OU Heat Exchange low 1 temperature (x10)
OU Heat Exchange low 2 temperature (x10)
OU Heat Exchange low 3 temperature (x10)
OU Heat Exchange low 4 temperature (x10)
OU Heat exchange high 1 temperature (x10)
OU Heat exchange high 2 temperature (x10)
OU Heat exchange high 3 temperature (x10)
OU Heat exchange high 4 temperature (x10)
OU Unit temperature (x10)
OU Discharge pipe temperature 1 (x10)
OU Discharge pipe temperature 2 (x10)
OU Crankcase 1 temperature (x10)
OU Crankcase 2 temperature (x10)
OU Compressor current 1 (x10)
OU Compressor current 2 (x10)
OU High pressure (x100)
OU Low pressure (x100)
Register name
0-No Error, 1-Error
0-Off, 1-On
0-Cool, 1-Heat, 2-Fan, 3-Auto, 4-Dry
16 .. 30ºC / 60 .. 86ºF
0-Low, 1-Medium, 2-High, 3-Powerful
0-Unlock, 1-Lock
0-Swing, 1-Pos1, 2-Pos2, 3-Pos3, 4-Pos4
0 .. 30ºC / 32 .. 86ºF
0-Off, 1-On
0-No Error, X (1.. 255)-Error
0-Off, 1-On
1-Reset
1-Reset
Mitsubishi Heavy Industries VRF with KNX, Serial and IP support
Possible Values
0 .. 255Hz
0 .. 255Hz
ºC / ºF
ºC / ºF
ºC / ºF
ºC / ºF
ºC / ºF
ºC / ºF
ºC / ºF
ºC / ºF
ºC / ºF
ºC / ºF
ºC / ºF
ºC / ºF
ºC / ºF
Amperes
Amperes
MPa
MPa
Possible values
Page 25 of 36