Integration into KNX Systems
6.2. Integration into KNX Systems
6.2.1. KNX Signals
The following tables list all available KNX signals for this gateway.
NOTE
Physical Address: The gateway supports (P/S) and (P/I/S) format levels.
NOTICE
Communication object flags:
• Ri (Read on initialization): The gateway requests this signal's updated data after an initialization
instead of waiting for a change in the signal.
• R: The KNX system can read this signal.
• W: The KNX system can write this signal.
• T: The KNX system receives a telegram when this signal changes its value.
• U: This signal's data is updated after a reboot of either the gateway or the bus.
Table 4. Global signals
Description
Status_Gateway Communication Status
Control_On/Off (all units)
Control_Operating Mode (all units)
Control_Operating Mode (all units)
Control_Operating Mode (all units)
Control_Fan Speed (all units)
Control_Setpoint (all the units)
Control_Remote Lock/Unlock (all the units)
Table 5. Outdoor units
Description
Status_OU Compressor 1 Frequency
Status_OU Compressor 2 Frequency
Status_OU Heat Exchange low 1 temperature
Status_OU Heat Exchange low 2 temperature
Status_OU Heat Exchange low 3 temperature
Status_OU Heat Exchange low 4 temperature
Status_OU Heat Exchange high 1 temperature
Status_OU Heat Exchange high 2 temperature
Status_OU Heat Exchange high 3 temperature
Status_OU Heat Exchange high 4 temperature
USER MANUAL Version 1.2
Mitsubishi Heavy Industries VRF with KNX, Serial and IP support
Function
0-No Error, 1-Failure
0-Off, 1-On
0-Auto, 1-Heat, 3-Cool, 9-Fan, 14-Dry
0-Auto, 1-Heat, 2-Dry, 3-Fan, 4-Cool
0-Cool, 1-Heat, 2-Fan, 3-Dry, 4-Auto
0-Low, 1-Medium, 2-High, 3-Powerful
16..30ºC / 60..86ºF
0-Unlock, 1-Lock
Function
DPT
Hz
14.033-DPT_Value_Frequency (4byte)
Hz
14.033-DPT_Value_Frequency (4byte)
ºC / ºF
9.001/9.027-DPT_Value_Temp (2byte)
ºC / ºF
9.001/9.027-DPT_Value_Temp (2byte)
ºC / ºF
9.001/9.027-DPT_Value_Temp (2byte)
ºC / ºF
9.001/9.027-DPT_Value_Temp (2byte)
ºC / ºF
9.001/9.027-DPT_Value_Temp (2byte)
ºC / ºF
9.001/9.027-DPT_Value_Temp (2byte)
ºC / ºF
9.001/9.027-DPT_Value_Temp (2byte)
ºC / ºF
9.001/9.027-DPT_Value_Temp (2byte)
DPT
1.005-DPT_Alarm (1bit)
1.001-DPT_Switch (1bit)
20.105-DPT_HVACContrMode (1byte)
5.x (1byte)
5.x (1byte)
5.x (1byte)
9.001/9.027-DPT_Value_Temp (2byte)
1.002 DPT_Bool (1bit)
Flags
Unit ID
R, T
Unit 1 .. Unit 12
R, T
Unit 1 .. Unit 12
R, T
Unit 1 .. Unit 12
R, T
Unit 1 .. Unit 12
R, T
Unit 1 .. Unit 12
R, T
Unit 1 .. Unit 12
R, T
Unit 1 .. Unit 12
R, T
Unit 1 .. Unit 12
R, T
Unit 1 .. Unit 12
R, T
Unit 1 .. Unit 12
Flags
R, T
Ri, W, U
Ri, W, U
Ri, W, U
Ri, W, U
Ri, W, U
Ri, W, U
Ri, W, U
OU
1 .. 12
1 .. 12
1 .. 12
1 .. 12
1 .. 12
1 .. 12
1 .. 12
1 .. 12
1 .. 12
1 .. 12
Page 27 of 36