Fujitsu VRF systems with KNX, Serial and IP support
6.3. Integration into BACnet Systems
NOTICE
You can see the Protocol Implementation Conformance Statement (PICS) document on
6.3.1. BACnet Objects
NOTICE
This part is common for BACnet MS/TP and BACnet/IP.
Input object types:
• Binary input
Output object types:
• Binary output
• Multistate output
• Analog output
The following tables list all available BACnet objects for this gateway.
Table 8. Global signals
Object name
Possible values
0: Not used
Gateway_ES_C
1: Energy saving
0: Not used
Gateway_ES_S
1: Energy saving
0: Normal
Gateway_Error_S
1: Abnormal
1: No error
Gateway_ErrorCode_S
2: Hardware Comm. Error
3: No Config Error
0: Off
Batch_Operation_C
1: On
1: Cool
2: Heat
Batch_OperationMode_C
3: Fan
4: Dry
5: Auto
1: Low
2: High
3: Med
Batch_Fanspeed_C
4: Auto
5: Quiet
6: Med_Low
7: Med_High
Batch_SetTemp_C
°C / °F
1: No disabled
Batch_RC_Prohibition_C
0: Disabled
Page 32 of 41
Object type
Object instance
4-Binary Output
0
3-Binary Input
0
3-Binary Input
1
13-Multistate Input
0
4-Binary Output
1
14-Multistate Output
0
14-Multistate Output
1
1-Analog Input
0
14-Multistate Output
2
Integration into BACnet Systems
USER MANUAL Version 1.0.7
Need help?
Do you have a question about the Intesis IN775FGL00XO000 and is the answer not in the manual?
Questions and answers