HMS Networks Intesis IN776MHI00XO000 User Manual page 35

Mitsubishi heavy industries vrf with knx, serial and ip support
Table of Contents

Advertisement

Mitsubishi Heavy Industries VRF with KNX, Serial and IP support
Object instance
(OU[1 .. 12]*20) + 10000 + 17
0-Analog Input
(OU[1 .. 12]*20) + 10000 + 18
0-Analog Input
Table 9. Indoor units
Object instance
Type
(IU[1 .. 128]*25) + 0
3-Binary Input
(IU[1 .. 128]*25) + 1
3-Binary Input
(IU[1 .. 128]*25) + 0
4-Binary Output
(IU[1 .. 128]*25) + 0
13-Multistate Input
(IU[1 .. 128]*25) + 0
14-Multistate Output
(IU[1 .. 128]*25) + 0
0-Analog Input
(IU[1 .. 128]*25) + 0
1-Analog Output
(IU[1 .. 128]*25) + 1
13-Multistate Input
(IU[1 .. 128]*25) + 1
14-Multistate Output
(IU[1 .. 128]*25) + 2
3-Binary Input
(IU[1 .. 128]*25) + 1
4-Binary Output
(IU[1 .. 128]*25) + 2
13-Multistate Input
(IU[1 .. 128]*25) + 2
14-Multistate Output
(IU[1 .. 128]*25) + 1
0-Analog Input
(IU[1 .. 128]*25) + 3
3-Binary Input
(IU[1 .. 128]*25) + 2
0-Analog Input
(IU[1 .. 128]*25) + 4
3-Binary Input
(IU[1 .. 128]*25) + 2
4-Binary Output
(IU[1 .. 128]*25) + 3
4-Binary Output
(IU[1 .. 128]*25) + 5
3-Binary Input
(IU[1 .. 128]*25) + 3
0-Analog Input
(IU[1 .. 128]*25) + 4
0-Analog Input
(IU[1 .. 128]*25) + 5
0-Analog Input
(IU[1 .. 128]*25) + 6
0-Analog Input
(IU[1 .. 128]*25) + 7
0-Analog Input
(IU[1 .. 128]*25) + 8
0-Analog Input
(IU[1 .. 128]*25) + 9
0-Analog Input
(IU[1 .. 128]*25) + 10
0-Analog Input
(IU[1 .. 128]*25) + 11
0-Analog Input
Page 32 of 36
Type
Possible values
MPa
OUXX_High pressure
MPa
OUXX_Low pressure
Possible values
0-No Error, 1-Error
0-Off,1-On
0-Off,1-On
1-Heat, 2-Cool,3-Fan,4-
Dry,5-Auto
1-Heat,2-Cool,3-Fan,4-
Dry,5-Auto
ºC / ºF
ºC / ºF
1-Low, 2-Medium, 3-High, 4-
Powerful
1-Low, 2-Medium, 3-High, 4-
Powerful
0-Unlock, 1-Lock
0-Unlock, 1-Lock
1-Swing, 2-Pos1, 3-Pos2, 4-
Pos3, 5-Pos4
1-Swing, 2-Pos1, 3-Pos2, 4-
Pos3, 5-Pos4
ºC / ºF
0-Off,1-On
0-No Error, X-Error(0..255)
0-Off,1-On
0-No reset, 1-Reset
0-No reset, 1-Reset
0-Off,1-On
000..999
0..255 Hz
0..255 Hz
ºC / ºF
ºC / ºF
ºC / ºF
kWh
kWh
kWh
Integration into BACnet Systems
Object name
Object name
OXXUXX_Communication Status_S
OXXUXX_On/Off_S
OXXUXX_On/Off_C
OXXUXX_Operation Mode_S
OXXUXX_Operation Mode_C
OXXUXX_Temperature Setpoint_S
OXXUXX_Temperature Setpoint_C
OXXUXX_FanSpeed_S
OXXUXX_FanSpeed_C
OXXUXX_Remote Lock_S
OXXUXX_Remote Lock_C
OXXUXX_Louver / Vane Position_S
OXXUXX_Louver / Vane Position_C
OXXUXX_Room Temperature_S
OXXUXX_Filter Sign_S
OXXUXX_Unit Error code_S
OXXUXX_Compressor_S
OXXUXX_Filter Sign Reset_C
OXXUXX_RC Error Reset_C
OXXUXX_Thermo On/Off_S
OXXUXX_Expansion valve opening
pulse_S
OXXUXX_Decision frequency_S
OXXUXX_Demand frequency_S
OXXUXX_Heat Exchange low 1
temperature_S
OXXUXX_Heat Exchange low 2
temperature_S
OXXUXX_Heat Exchange low 3
temperature_S
OXXUXX_Consumption Yesterday_S
OXXUXX_Consumption Today_S
OXXUXX_Consumption Total_S
Unit ID
OU
Unit 1 .. Unit 12
1 .. 12
Unit 1 .. Unit 12
1 .. 12
Unit ID
IU
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
Unit 1 .. Unit 128
1 .. 128
USER MANUAL Version 1.2

Advertisement

Table of Contents
loading

Table of Contents