Integration into KNX Systems

6.2. Integration into KNX Systems

6.2.1. KNX

The following tables list all available KNX signals for this gateway.
NOTE
Physical Address: The gateway supports (P/S) and (P/I/S) format levels.
NOTICE
Communication object flags:
• Ri (Read on initialization): The gateway requests this signal's updated data after an initialization
instead of waiting for a change in the signal.
• R: The KNX system can read this signal.
• W: The KNX system can write this signal.
• T: The KNX system receives a telegram when this signal changes its value.
• U: This signal's data is updated after a reboot of either the gateway or the bus.
Table 5. Global signals
Description
Status_Gateway Communication Status
Control_On/Off (all units)
Control_Operating Mode (all units)
Control_Operating Mode (all units)
Control_Operating Mode (all units)
Control_Fan Speed (all units)
Control_Setpoint (all the units)
Control_Remote Lock/Unlock (all the units)
USER MANUAL Version 1.2.7
Mitsubishi Heavy Industries VRF with KNX, Serial and IP support
Function
0: No Error
1.005-DPT_Alarm (1bit)
1: Failure
0: Off
1.001-DPT_Switch (1bit)
1: On
0: Auto
20.105-DPT_HVACContrMode (1byte)
1: Heat
3: Cool
9: Fan
14: Dry
0: Auto
5.x (1byte)
1: Heat
2: Dry
3: Fan
4: Cool
0: Cool
5.x (1byte)
1: Heat
2: Fan
3: Dry
4: Auto
0: Low
5.x (1byte)
1: Medium
2: High
3: Powerful
Celsius: 16 .. 30°C
9.001/9.027-DPT_Value_Temp (2byte)
Fahrenheit: 60 .. 86°F
0: Unlock
1.002 DPT_Bool (1bit)
1: Lock
DPT
Flags
R, T
W
W
W
W
W
W
W