Samsung NASA with KNX, Serial and IP support
6.2. Integration into KNX Systems
6.2.1. KNX Signals
The following tables list all available KNX signals for this gateway.
NOTE
Physical Address: The gateway supports (P/S) and (P/I/S) format levels.
NOTICE
Communication object flags:
• Ri (Read on initialization): The gateway requests this signal's updated data after an initialization
instead of waiting for a change in the signal.
• R: The KNX system can read this signal.
• W: The KNX system can write this signal.
• T: The KNX system receives a telegram when this signal changes its value.
• U: This signal's data is updated after a reboot of either the gateway or the bus.
Table 5. Alarm signals
Object name
Status_OUXX_Communication Error OU
Status_OU Addressing Error
Table 6. Global signals
Object name
On/Off (all units)
Operating Mode (all units)
Operating Mode (all units)
Page 26 of 44
Possible values
0: No error
1: Error
0: OU Addressing OK
1: Manual Addr in OU required
Possible values
0: Off
1: On
0: Auto
1: Heat
3: Cool
9: Fan
14: Dry
0: Auto
1: Heat
2: Dry
3: Fan
4: Cool
5: Cool Storage
6: Heat Storage
Integration into KNX Systems
DPT
1.005-DPT_Alarm (1bit)
1.005-DPT_Alarm (1bit)
DPT
1.001-DPT_Switch (1bit)
20.105-DPT_HVACContrMode (1byte)
5.x (1byte)
USER MANUAL Version 1.0.6
Flags
R, T
R, T
Flags
W
W
W