Commissioning - Gira One 5065 00 Operating Instructions Manual

Dimming actuator 1-gang 200 w with binary input, 3-gang
Table of Contents

Advertisement

Dimming actuator 1-gang 200 W with binary input, 3-gang
Observe ambient temperature. Ensure adequate cooling.
Connect bus line, observing the correct polarity.
Connect load as shown in the connection example (see figure 5).
If required, connect potential-free contacts or condensation/leakage sensors to
inputs 1...3, or NTC temperature sensors to input 3 (see figure 2).
Install the device in the appliance box.
The COM reference potential must not be connected together with COM con-
nections of other devices!
4.2

Commissioning

Commissioning the device
Delivery state: The output is set to the universal dimming principle with automatic re-
cognition of the load type. Operation of the output is possible via input 1 (ON/
Brighter) and input 2 (OFF/Darker). Input 3 has no function.
Function of Inputs in the as-delivered state
Input
1
1
2
2
3
The device is commissioned with the Gira Project Assistant (GPA) version 5 or
higher.
Safe-state mode
The safe-state mode stops the execution of the program.
Only the system software of the device is still functional. Diagnosis functions and pro-
gramming of the device are possible.
Activating safe-state mode
Switch off the bus voltage or disconnect the device from the bus.
Wait about 10 s.
Press and hold down the programming button.
Switch on the bus voltage or connect the bus again at the device. Release the
programming button only after the programming LED starts flashing slowly.
The safe-state mode is activated.
82404412
Push-button (NO con-
tact)
Press briefly (< 0.4 s)
Press for a long time (>
0.4 s)
Press briefly (< 0.4 s)
Press for a long time (>
0.4 s)
---
02.12.2022
Function
Switch on
Increase brightness
Switch off
Reduce brightness
---
9 / 19