3-22
Chapter 3: Configuring the 2085sc-IF16 Using CCW
Mod_Error
Extended_Error_Info
[11:9]
[8:0] (hex)
(binary)
001
104
001
105
001
106
001
107
3.3.15 Module Specific Channel Configuration Errors
Mod_Err
Extended_Error_Info [8:0]
or [11:9]
Reserve
(binary)
d [8]
(binary)
010
0
010
0
010
0
010
0
User's Manual Pub. 0300306-01 Rev. A
Combined
[11:0]
(hex)
304
305
306
307
The following table lists module specific channel configuration errors for the
2085sc-IF16.
For the module specific configuration errors, the Extended_Errror_Info (bits 0 –
8) field is further divided as follows:
Bits 0–3 indicate the channel (0–15) that has the configuration error. If
multiple channels have an error, only the first channel that has the error
is reported.
Bits 4–7 indicate the specific channel configuration error.
Bit 8 is 0 to indicate a channel configuration error.
Error
Channel
[7:4]
[3:0] (binary)
(binary)
0000
0000
0001
0000–1111
0010
0000–1111
0011
0000–1111
Description
ADC communication error
This hardware error is set if the module detects the
analog-to-digital converter is not functioning
properly.
(Unused by the 2085sc-IF16)
ASIC communication error
This hardware error is set if a communications
error to the ASIC from the microcontroller has
been detected.
Checksum error
This hardware error is set if the calibration data
stored in the module is missing or corrupted.
Combined
Description
[11:0]
(hex)
400
General channel configuration
error, no additional information
410–41f
Invalid Input Range selection
Check the Range Type setting in the
Channel Configuration data.
420–42f
Invalid Input ADC Filter
selection
Check the ADC Filter setting in the
Channel Configuration data.
430–43f
Invalid Input Data Format
selection
Check the Data Format setting in
the Channel Configuration data.
Need help?