Output Assembly - Spectrum Controls Micro850 User Manual

16-channel analog input module
Table of Contents

Advertisement

3-18
Chapter 3: Configuring the 2085sc-IF16 Using CCW
3.3.9 Module Status Struct
Bit
Name
Bit 0-12
(unused)
Bit 13
Invalid Serial Number Data 0: Serial Number Valid
Bit 14
Invalid Calibration Data
Bit 15
Module Fault

3.3.10 Output Assembly

Word
Bit
Output 0
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
User's Manual Pub. 0300306-01 Rev. A
The structure definition for the 'Module Status' word in the Input Assembly table
is described below. Unused bits are 0.
Description
(unused)
1: Serial Number Invalid
This bit is set if the factory-programmed serial number data is
missing or has become corrupt.
0: Calibration Valid
1: Calibration Invalid
This bit is set if the module's calibration data has not been
programmed or has become corrupt.
0: No Fault
1: Fault
This bit is set if any of the above bits are set or if any channel
has its fault bit set.
The Output array is organized as follows:
Name
Ch 0 Process Alarm High Latch Clear
Ch 0 Process Alarm Low Latch Clear
Ch 1 Process Alarm High Latch Clear
Ch 1 Process Alarm Low Latch Clear
Ch 2 Process Alarm High Latch Clear
Ch 2 Process Alarm Low Latch Clear
Ch 3 Process Alarm High Latch Clear
Ch 3 Process Alarm Low Latch Clear
Ch 4 Process Alarm High Latch Clear
Description
0: Normal Operation
1: Clear Alarm Latch
0: Normal Operation
1: Clear Alarm Latch
0: Normal Operation
1: Clear Alarm Latch
0: Normal Operation
1: Clear Alarm Latch
0: Normal Operation
1: Clear Alarm Latch
0: Normal Operation
1: Clear Alarm Latch
0: Normal Operation
1: Clear Alarm Latch
0: Normal Operation
1: Clear Alarm Latch
0: Normal Operation
1: Clear Alarm Latch