Input Range
Signal
-10 to +10 V
Low Limit
(IF16V only)
Low Range
High Range
High Limit
0 to 10 V
Low Limit
(IF16V only)
Low Range
High Range
High Limit
0 to 5 V
Low Limit
(IF16V only)
Low Range
High Range
High Limit
4 to 20 mA
Low Limit
(IF16C only)
Low Range
High Range
High Limit
0 to 20 mA
Low Limit
(IF16C only)
Low Range
High Range
High Limit
Chapter 3: Configuring the 2085sc-IF16 Using CCW
Once a module receives its configuration, the range scaling feature is always
active:
Raw/
Proportional
-10.500 V
-32768
-10.000 V
-31208
+10.000 V
31207
+10.500 V
32767
-0.500 V
-32768
0.000 V
-29789
+10.000 V
29788
+10.500 V
32767
-0.500 V
-32768
0.000 V
-27069
+5.000 V
29918
+5.250 V
32767
+3.200 mA
-32768
+4.000 mA
-29823
+20.000 mA
29085
+21.000 mA
32767
+0.000 mA
-32768
+0.000 mA
-32768
+20.000 mA
29646
+21.000 mA
32767
Process Alarms
Process alarms allow you to specify alarm limits for the input signal, and to have
the module report when those signal limits have been exceeded. The feature is
active if enabled in the channel(s) configuration.
To set up, input the desired alarm values (Enable Process Alarms, Process Alarm
Latch, Process Alarm High Value, Process Alarm Low Value) for each channel
into the configuration table, as described in Configuration Assembly. Report a
configuration error if any alarm value in the configuration table has been set
incorrectly.
Set the Process Alarm High status bit in the channel status struct when the
channel input value is greater than the Process Alarm High Value in the
configuration table.
Set the Process Alarm Low status bit in the channel status struct when the
channel input value is less than the Process Alarm Low Value in the
configuration table.
If the Process Alarm Latch bit is disabled, then clear the appropriate
alarm status bit when the channel input value is no longer within the
alarm value range.
Engineering
Engineering
×
×
Units
1
Units
10
-10500
-1050
-10000
-1000
10000
1000
10500
1050
-500
-50
0
0
10000
1000
10500
1050
-500
-50
0
0
5000
500
5250
525
3200
320
4000
400
20000
2000
21000
2100
0
0
0
0
20000
2000
21000
2100
User's Manual Pub. 0300306-01 Rev. A
3-13
Percentage Full
Scale
-250
0
10000
10250
-500
0
10000
10500
-1000
0
10000
10500
-500
0
10000
10625
0
0
10000
10500
Need help?
Do you have a question about the Micro850 and is the answer not in the manual?