If the output frequency of the inverter is within the positive and negative amplitudes of the any
frequency reaching detection value, the corresponding digital output becomes ON.
F4.34
Zero current detection level
F4.35
Zero current detection delay time
If the output current of the inverter is equal to or less than the zero current detection level and the
duration exceeds the zero current detection delay time, the corresponding output terminal becomes ON. The
zero current detection is shown in the following figure .
F4.36
Output overcurrent threshold
Output overcurrent detection delay
F4.37
time
If the output current of the inverter is equal to or higher than the overcurrent threshold and the duration
exceeds the detection delay time, the corresponding output terminal becomes ON. The output overcurrent
detection function is shown in the following Figure .
F4.38
Any current reaching 1
Any current reaching 1
F4.39
F4.40
Any current reaching2
Any current reaching 2
F4.41
amplitude
amplitude
- 95 -
Chapter 7 Maintenance and Troubleshooting
Range:0.0%~300.0%
Range:0.01s~600.00s
Range: 0.0%~300.0%
Range:0.00s~600.00s
Range:0.0%~300.0%
Range:0.0%~300.0%
Range:0.0%~300.0%
Range:0.0%~300.0%
Default:5.0%
Default:0.10s
Default:200.0%
Default:0.00s
Default:100.0%
Default:0.0%
Default:100.0%
Default:0.0%