JT550 Series Inverter Manual
c) SOURCE Wiring
This wiring must jump the jumper J12 of PLC to COM, and Connect the + 24V and the COM terminal of the
external controller together. If you use an external power supply, the cathode of the power supply must be
connected to PLC.
d) Wiring of DO Terminal
When the digital output terminals need to drive the relay, an absorption diode shall be installed around the
relay coil. Otherwise, it may cause damage to the 24V DC power supply.
Note: The polarity of the absorption diode must be installed properly. As shown in Figure 3.9, failure to
comply will lead to burning the 24V DC power supply whenever the digital output terminal is active.
3.7 Major Circuit Terminals Screw Specs and Tightening Torque Standard
Inverter Powers
0.75-2.2kW
4.0-5.5kW
7.5-11kW
15-22kW
30-37kW
45-55kW
75-90kW
110-132kW
160-200kW
220-280kW
315-710kW
+VCC
R
PNP
信号
0V
External Controller
外部控制器
Figure 3.21 Wiring in SOURCE Mode
24V
AT500
JT550
Y1
YCM
Figure 3.22 DO Terminal Wiring Diagram
Terminal Specs
BA5-09-10.0-06
BA5-10-11.0-09
BA8-09-14.5-01-C
BA20-09-20.0-01
BA20-03-20.0-01
DRTB50-NR-09-CNNT
DRTB100-RHC-09-CNNT
RD300-01 600V 300A
SET420-B(Nut included)
SET630(Nut included)
SET630(Nut included)
24V
24V
PLC
X1
6K
X5
6K
COM
Control Board
of the Inverter
变频器控制板
Relay
继电器
Screw Specs
M4
M4
M5
M6
M6
M8
M10
M10
M12
M16
M16
- 35 -
Chapter 3 Electrical Installation
Diode
二极管
Torque Standard
2N.m
2N.m
4N.m
8N.m
8N.m
20N.m
35N.m
35N.m
60N.m
130N.m
130N.m